LEAK CHECK

Risk of burning or fire.
Serious burns to the skin or damage to property.
Do not use an open flame to check for function!
Leak check before start-up
Before start-up, check the product connections for leaks!
1. Close all shut-off fittings on the connected devices.
2. Slowly open the withdrawal valve or the gas cylinder valve(s).
3. If there is a safety device (e.g. EFV) between the tank and the connected device(s),
open this during the leak check.
4. Spray all connections with a foam producing substance according to EN 14291
(e.g. leak detector spray, Part no. 02 601 00).
5. Bubbles will form in the foam producing substance if there are any leaks.
If bubbles form, tighten the connections (see ASSEMBLY). If the leaks cannot be
repaired, the product must not be used.
For testing at the test connection, we recommend the leak and function tester type DFP25
(Part no. 02 617 05).

START-UP

After the product has been ASSEMBLED and LEAK TESTING has been carried out
successfully, it is immediately ready for operation.

TROUBLESHOOTING

Fault cause
Gas smell
Leaking LPG is extremely
flammable.
Can cause explosions.
Abnormal flame pattern of
non-adjustable pressure
regulator
No gas flow
12 / 16
Double‐stage tank regulator PS 25 bar
Action
 Close the gas supply.
 Do not use any electric switches.
 Do not use a phone in the building.
 Ventilate rooms well.
 Shut down the LPG system.
 Contact a specialised company.
Compare the nominal outlet pressure with the nominal
connection pressure:
 if they do not correspond, replace the pressure regulator
or the gas appliance
Measure the outlet pressure; outlet pressure is not within
the specified limits:
 check the system configuration, cleanse the filter screen
as an option  pressure regulator is defective, replace
Gas feed is closed:
 open the gas cylinder valve or the shut-off fittings
Safety overpressure shut-off valve (OPSO) is closed:
 carry out the steps described in "Restarting the safety
overpressure shut-off valve (OPSO)"
UPSO / EFV is closed:
 carry out the steps described in "Restarting UPSO / EFV"
Filter sieve in the input connection is dirty:
 send the pressure regulator to the manufacturer to be
checked