Herunterladen Inhalt Inhalt Diese Seite drucken

GOK BHK/K EFV Montage- Und Bedienungsanleitung Seite 22

Behälterregler-kombination ps 25 bar/durchgangsform zum direktanschluss as gasbehälter
Inhaltsverzeichnis

Werbung

Verfügbare Sprachen
  • DE

Verfügbare Sprachen

  • DEUTSCH, seite 1
Excess flow valve (EFV) option
The excess flow valve (EFV) is a safety device that blocks the gas flow if the flow rate is >
110% than the target value of the pressure regulator. This can be caused, for example, by a
burst pipe or hose.
INFORMATION ABOUT THE EXCESS FLOW VALVE (EFV)
EFV – Excess Flow Valve
Name for integrated excess flow device according to EN 16129.
If the UPSO or EFV responds, the gas feed can be restored again, the gas flow is restored
manually when the conditions that triggered the safety device are no longer present by
following the steps in "Restarting the OPSO / UPSO or UPSO / EFV with visual indicator".
"UPSO" and or "EFV" are marked on the type label of the pressure regulator.
Pipe dimensions
To ensure that the pressure regulator functions as intended (UPSO and EFV), the following
dimensions are recommended:
• For a flow rate of 6 kg/h:
Pipe material
Steel
Copper
Steel
Steel
Copper
PE-HD
Elbows, branches, valves etc. must be deducted from the length [m].
• For a flow rate of 12 kg/h:
Pipe material
Steel
Steel
Copper
PE-HD
Elbows, branches, valves etc. must be deducted from the length [m].
If the pipe cross-section is smaller or the length greater, the functions of the pressure
regulator are no longer guaranteed.
Check the supply pressure p
the connected device.
Test connector option
A leak tester can be connected to the test connector for pressure and leak tests. First, loosen
the set screw in the test connector. When you have used it, tighten the set screw again and
check for leaks again. See LEAK CHECK.
6 / 16
Outside diameter
x wall thickness [mm]
Ø 18 x 1.5
Ø 18 x 1
Ø 22 x 2
Ø 22 x 1.5
Ø 22 x 1
Ø 32 x 2.9
Outside diameter
x wall thickness [mm]
Ø 22 x 2
Ø 22 x 1.5
Ø 22 x 1
Ø 32 x 2.9
according to EN 16129 Table 5 (≥ 42.5 mbar) upstream from
min
Double‐stage tank regulator PS 25 bar
Length [m] at ∆P5
10
15
25
30
35
65
Length [m] at ∆P5
8
10
12
35

Quicklinks ausblenden:

Werbung

Inhaltsverzeichnis

Fehlerbehebung

loading

Diese Anleitung auch für:

Bhk/kBhk 052bBhk 052

Inhaltsverzeichnis