Herunterladen Inhalt Inhalt Diese Seite drucken

Electrical Connection - Siemens SIPART PS2 Handbuch

Vorschau ausblenden Andere Handbücher für SIPART PS2:
Inhaltsverzeichnis

Werbung

Verfügbare Sprachen

Verfügbare Sprachen

Preparing for Operation
3.2

Electrical Connection

You require the EMC filter module order number C73451-A430-D23 for the
electrical connection. The SIPART PS2 positioner supplies power to the
NCS via the EMC filter module. Proceed as follows to connect the shielded
four-pole cable of the NCS to the SIPART PS2 positioner:
1.
Replace the dummy stopper on the SIPART PS2 positioner with the
sxcre-type cable gland supplied with the EMC filter module.
NOTE
Use the blue screw-type cable gland for Ex devices and the gray gland for
non-Ex devices.
2.
Lay the stripped NCS-cable from the outside through the opening in the
screw-type cable gland with the two openings into the SIPART PS2
positioner. If you do not need the second opening in the screw-type
cable gland, seal this with the enclosed stopper.
3.
Screw on the screw-type cable gland tight.
4.
Clamp the colored wires of the cable in the following order (see Figure
8, page 57) to the terminal of the EMC filter module:
− yellow
− green
− white or
black
− brown
5.
Connect the terminal end of the cable shield with a screw to the
grounding point of the positioner.
56
top terminal (Vcc)
terminal below the top terminal (Vref)
terminal above the bottom terminal (Vpos)
bottom terminal (GND)
Operating Instructions
NCS
A5E00097485-06