Herunterladen Inhalt Inhalt Diese Seite drucken

Configuration Using The Micropulse Configuration Tool (Only For Btl7-S510(B); Micropulse Configuration Tool (Software); Connecting The Usb Communication Box; Configuration Options - Balluff BTL7-S5 Betriebsanleitung

Vorschau ausblenden Andere Handbücher für BTL7-S5:
Inhaltsverzeichnis

Werbung

Verfügbare Sprachen
  • DE

Verfügbare Sprachen

  • DEUTSCH, seite 1
BTL7-S5 _ _ (B)-M _ _ _ _ -A/B/Y/Z(8)-S32/S115/S140/S147/KA _ _ /FA _ _
Micropulse Transducer - Rod Style
7

Configuration using the Micropulse Configuration Tool (only for BTL7-S510(B)-...)

7.1

Micropulse Configuration Tool (software)

The BTL7-S510(B)-... transducer can be configured
quickly and simply on a PC using the Micropulse
Configuration Tool PC software.
The most important features include:
Online display of the current position of the magnet
Graphic support for setting the functions and
characteristics
Display of information on the connected transducer
Selection of displayed number formats and units
Possible to reset to the factory settings
Demo mode without a connected transducer
The PC software and associated manual can
be found in the Internet under
www.balluff.com/downloads-btl7.
7.2

Connecting the USB communication box

With BTL7-S510(B)-... transducers with a connector (S32/
S115/S140), the communication box must be looped in
between the transducer and controller. The communication
box is connected to the PC via a USB cable.
USB cable
Connection cable approx. 0.3 m
with connector (socket)
8-pin
Fig. 7-1: Connecting the communication box with connector
With a BTL7-S510(B)-...-cable transducer, the
communication lines La, Lb and GND are connected to the
USB communication box.
USB cable
Fig. 7-2: Connecting the communication box with a cable connection
When reading or writing data via the
Configuration Tool, the LED 2 flashes green.
www.balluff.com
Connection cable
approx. 0.3 m with
connector (plug)
Controller
6-pin
Controller
8-pin
Connection cable
approx. 0.6 m with
luster terminal
7.3

Configuration options

Prerequisites
USB communication box connected to the transducer
and PC.
Software correctly installed.
Transducer connected to the power supply.
Magnet on transducer.
Output functions
Position: Position in the measuring range.
Speed: Speed of the magnet; the sign indicates the
direction of movement. A movement from the starting
point to end point is output with a positive sign; a
movement from the end point to the starting point is
output with a negative sign.
Speed (unsigned): Speed of the magnet, the direction
of movement cannot be read.
Differential position: Distance between two magnets.
Selection is only possible if two magnets have been
selected.
Speed difference: The speeds of two magnets are
subtracted to form a sum. Selection is only possible if
two magnets have been selected.
Freely configurable characteristic curve
The gradient of the characteristic curve can be set by
adjusting the resolution.
The limits can be adjusted to the measuring range.
The error value can be set.
Boundary conditions for several magnets
Two magnets can only be selected from a nominal
length ≥ 90 mm.
The distance between two magnets must be ≥ 65 mm.
DANGER
Uncontrolled system movement
When starting up, if the position measuring system is
part of a closed loop system whose parameters have not
yet been set, the system may perform uncontrolled
movements. This could result in personal injury and
equipment damage.
► The system must be taken out of operation before
configuration.
► Transducers may only be connected to the
communication box for configuration.
► The communication box must be removed after
configuration.
english
17

Quicklinks ausblenden:

Werbung

Inhaltsverzeichnis
loading

Inhaltsverzeichnis