5 Technical Data

5.1 Specifications

Parameters
AC
Max. generator power
Nominal apparent power
2)
Nominal active power
1)
Reactive power range
Nominal AC voltage
Supported grounding systems
Nominal AC current
Max. AC current at 400 Vac
AC total harmonic distortion (THD at nominal output power)
Power factor – standard
Displacement power factor
Stand-by power consumption (for communication)
Nominal grid frequency (range)
DC
Input voltage range (at 400 Vac / at 480 Vac)
Nominal voltage DC (at 400 Vac / at 480 Vac)
MPP voltage range (at 400 Vac / at 480 Vac)
Startup voltage (at 400 Vac / at 480 Vac)
Max. input voltage
Min. power on the grid
Max. input current / max. short-circuit current
Number of independent MPP inputs /
strings per MPP input
Overvoltage categories
Integrable DC surge arrester / AC surge arrester
Efficiency
Max. efficiency
EU efficiency
MPPT efficiency, static
Installation Guide
1)
SHP 75-10
112500 W
75000 VA
75000 W
0 to 75000 var
3 / PE; 400 V (50 Hz)
TT, TN
3 x 109 A
3 x 109 A
< 3 %
> 0.99 at nominal power
0 overexcited to 0 underexcited
< 3 W
50 Hz/60 Hz (± 10%)
565 V to 1000 V / 680 V to 1000 V
630 V/710 V
570 V to 800 V / 685 V to 800 V
600 V/720 V
1000 V
100 W
140 A / 210 A
1/1 (split up by external PV array junction box)
AC: Overvoltage category III (OVC III),
PV: Overvoltage category II (OVC II)
Type II / type II + III (combined)
98.8 %
98.2 %
99.9 %
SHP75-10-IA-xx-10