REMOTE CONTROLLER OPERATION

8
DSW8: (Not used)
No setting is required, due to setting before shipment.
Setting position before shipment is all OFF.
NOTE:
The mark " " indicates position of dips switches. Figures
-
show setting before shipment or after selection.
6 REMOTE CONTROLLER OPERATION
6.1. SETTING THE FILTER INDICATION INTERVAL
The FILTER interval indication on the remote control
Switch (PC-P1HE) can be set approximately at 100, 1,200
or 2,500 hours (factory setting: 1,200 hours). If 100 or
2,500 hours is required, follow the instructions below.
Step 1: Changing to Optional Setting Mode
Press the CHECK switch and the RESET switch together
more than 3 seconds while the unit is stopped. The
operation mode is changed to the field setting mode,
"SERVICE" is indicated and "
indicated, press the  or  switch and set "
condition, press the CHECK switch and the mode is
changed to the optional setting mode.
Flickered (Press  or  switch)

Step 2: Selection of Indoor Unit for Optional
Setting
When the mode is changed to the optional setting mode,
the indication on the liquid crystal display is as shown
below.
 The flickering indication of "
 The address of the Indoor Unit for optional setting is
indicated.
" flickers. When "
" is not


". In this

"stops.

SW1: (Not used)
No setting is required due to setting before shipment.
Setting position before shipment is "2".
 The address of the refrigerant system for optional setting
is indicated.
Select the Indoor Unit to be set by pressing the  or 
switch and indicate the address of the Indoor Unit. In this
condition, press the CHECK switch and the indication is
changed to the indication of optional setting:
NOTE:
In case that the both indications of the ADDS. (Address)
-
and RN. (Refrigerant Cycle Number) show "", the
same setting is performed to all the indoor units.
The indoor units not connected are not indicated.
-
Step 3: Optional Setting Items and Changing
Setting Conditions
The indication of optional setting is as shown below.
 The code of optional setting is as shown below
 The indications of ADDS. and RN. are turned OFF and
the optional setting condition is indicated.
The item code of optional setting is changed by pressing
the TIME  or  switch. The optional setting condition is
changed by pressing the CHECK switch. Set the item code
"". In case of setting other indoor unit, press the  or 
switch and the indication is changed to the condition of the
item "Step 2 Selection of Indoor Unit for Optional Setting".