English / Instruction
Table 1
Modbus actuator
1.
VAV damper, exhaust
2.
VAV damper, inlet
3.
VAV damper, inlet
4.
Cooling valve
5.
Heating valve
Combination valve
6.
(heating/cooling)
7.
6 way valve (heating/cooling)
Modbus address and communication parameters are set in Belimo actuators using
the Servicetool ZTH-EU programming unit from Belimo. The Modbus communication
protocol is 38.4 kBaud, 1 start bit, 8 data bits, 2 stop bits and no parity (see example
of ZTH-EU menu settings for VAV actuators in fig. 22). Instructions for setting Modbus
addresses in Belimo actuators can be found at www.belimo.eu.
LED indications "D" (see figs 3 and 15)
OJ GreenZone™ Module M is equipped with five LEDs, which indicate the status of the
Modbus actuators (see table 2).
Table 2
 
LED
1.
2.
 
3.
4.
 
 
5.
 
4 and 5
NOTE!
• A flashing LED indicates that the actuator is correctly connected and addressed.
• An inactive LED indicates that the actuator is not installed, not connected correctly or
not addressed correctly on the actuator itself.
• LEDs 4 and 5 flashing simultaneously indicates that the actuator on the combination
valve/6 way valve is connected correctly and that Modbus communication is OK.
6
Off
Nothing connected
Nothing connected
Nothing connected
Nothing connected
Nothing connected
© 2017 OJ Electronics A/S
Modbus address
Flashing
VAV damper, exhaust = Communication OK
VAV damper, inlet = Communication OK
VAV damper, inlet = Communication OK
Heating valve = Communication OK
Cooling valve = Communication OK
Combination/6 way valve = Communication OK