4

Intended use

This device must not be operated by persons (including children)
with limited physical, sensory or mental abilities or lacking the
necessary experience and/or knowledge.
Children must be supervised to ensure that they do not play with
the device.
These high-efficiency pumps are intended for the circulation of
liquids (no oils, liquids containing oil, no foodstuff) in:
Domestic hot water heating systems
Air conditioning, cooling and cold water circuits
5

Information on the product

5.1 Technical data

Supply voltage
Motor protection
Degree of protection
Heat class
Relative humidity
System pressure
Supply pressure
EMC
Sound pressure level
Ambient temperature
Temperature class
Surface temperature
Media temperature
ATTENTION!
Risk of material damage!
If impermissible media are pumped, the pump may be destroyed.

5.2 Media to be pumped

Pure, thin liquid, non-aggressive and non-explosive media with
no solid or long fibre components and free from admixtures of
mineral oils.
In heating systems, the water should fulfil the requirements of
current valid standards, which apply for the water quality in
heating systems (e.g. VDI 2035).
www.dimplex.de
Danger of damage to health! 
The materials used in the UPH-60 can cause damage to health as they are
not approved for use in domestic water circulating systems. Do not use
UPH-60 pumps in domestic water systems.
1 x 230 V – 10 %/+ 6 %, 50 Hz, PE
The pump requires no external motor protection.
IP 42
F
Max. 95 %
Max. 1.0 MPa, 10 bar, 102 m
Media temperature
+75 °C
+90 °C
+110 °C
EN 61000-6-2 and EN 61000-6-3
The sound pressure level of the pump is lower than 43 dB(A).
0 ? to +40 ?
TF110 in accordance with CEN 335-2-51
The maximum surface temperature will not exceed +125 °C.
+2 °C to +110 °C
To prevent condensate formation in the terminal box and stator, the media temperature must always be higher
than the ambient temperature.
Ambient temperature
[°C]
0
10
20
30
35
40
The pump must not be used to convey inflammable media, such as diesel
oil and petrol.
452115.66.16 FD 9206
Heat pumps
Solar energy systems
Closed industrial circulating systems.
ATTENTION!
Minimum supply pressure
0.05 bar, 0.005 MPa, 0.5 m
0.28 bar, 0.028 MPa, 2.8 m
1.08 bar, 0.108 MPa, 10.8 m
Media temperature
Min.
[°C]
2
10
20
30
35
40
ATTENTION!
UPH 60-25 - UPH 60-32
Max.
[°C]
110
110
110
110
90
70
EN-3
Inhaltsverzeichnis