Connection examples

1. Light without neutral conductor
3. Connection using an indoor two-way switch
for manual override and automatic operation
Setting I: Automatic operation
Setting II: Manual operation, light permanently ON
Note: The system cannot be switched OFF, it is
only possible to select operation at setting I or II.
1) e. g. 1-4 x 100 W incandescent lamps
2) load, lighting 1000 W max. (refer to Technical specifi cations)
3) IS 2180-5 connection terminals
4) Indoor switch
5) Indoor two-circuit single interruption switch, manual operation, automatic operation
6) Indoor two-way switch, automatic operation, manual override
Operation/Maintenance
The infrared sensor can be
Weather conditions may
used for switching light ON
affect the way the motion
and OFF automatically. The
detector works. Strong gusts
unit is not suitable for burglar
of wind, snow, rain or hail
alarm systems as it is not
may cause the light to come
tamperproof in the manner
ON when it is not wanted be-
prescribed for such systems.
cause the sensor is unable to
2. Light with neutral conductor
distinguish sudden changes
of temperature from sources
of heat. The detector lens
may be cleaned with a damp
cloth if it gets dirty (do not
use cleaning agents).
20

Troubleshooting

Malfunction
Cause
a
IS 2180-5 without power
Fuse faulty, not switched
ON
a
Short circuit
a
Mains switch OFF
a
IS 2180-5 will not switch ON
Twilight setting in night-
time mode during daytime
operation
a
Bulb faulty
a
Mains switch OFF
a
Fuse faulty
a
Detection zone not
properly targeted
a
IS 2180-5 will not switch OFF
Continued movement in
detection zone
a
Light being operated is
located in detection zone
and keeps switching ON
as a result of temperature
change
a
Set to continuous opera-
tion by indoor two-circuit
single interruption switch
a
IS 2180-5 keeps switching
Lamp being operated in
ON/OFF
located the detection zone
a
Animals moving in
detection zone
a
Heat source (e.g. extractor
hood outlet) in detection
zone
a
IS 2180-5 switches ON when
Wind is moving trees and
it should not
bushes in the detection
zone
a
Cars in the street are be-
ing detected
a
Sudden temperature
changes due to weather
(wind, rain, snow) or air
expelled from fans, open
windows
Remedy
a
Replace fuse, turn ON
mains switch, check lead
with voltage tester
a
Check connections
a
Switch ON
a
Adjust setting
a
Change bulb
a
Switch ON
a
Fit new fuse, check
connection if necessary
a
Re-adjust
a
Check detection zone and
re-adjust if necessary or fi t
shrouds
a
Adjust detection zone or fi t
shrouds
a
Set two-circuit single inter-
ruption switch to automat-
ic operation
a
Adjust detection zone or fi t
shrouds, increase distance
a
Adjust detection zone or fi t
shrouds
a
Adjust detection zone or fi t
shrouds
a
Fit shrouds to mask out
zones
a
Fit shrouds to mask out
zones
a
Change zone, move site of
installation
21