6.4.1

Installation procedure

1 Prepare the surface where the unit is to be mounted.
Make sure that the surface is flat, levelled and that it
supports the weight of the unit. Perform the installa-
tion in accordance with local rules and regulations.
2 Place the unit standing on the floor. Use the enclosed
adjustable feet to level the unit
Caution
Beware of sharp edges during mounting
and maintenance. Use protective gloves
3 Connect the condensate drainage to the drain plug in
the bottom of the unit. Make sure to use correct drain
trap. The height (H) must be at least 60 mm. Drain
traps are not included on delivery and can not be ob-
tained from Systemair.
4 Connect the unit to the duct system. Make sure that
all necessary accessories are used to create a func-
tional ventilation solution.
Important
The installation of the unit and complete
ventilation system must be performed by
an authorized installer and in accordance
with local rules and regulations.
5 Connect the control panel to the socket on top of the
unit (chapter 7.2).
6 Connect the unit electrically to a main outlet using the
provided plug and check that it starts up correctly.