• In REGULAR MODE the status will display the total number of jobs recorded and that the status
of recording is OFF.
R
NOTE: When the manifold is in the last hour of recording and the user performs a check status
command the 0 that will be displayed shall be flashing to indicate that the recording capacity is
approaching the limit.
EXITING RECORDING MODE
Once sufficient data has been recorded exit the recording mode by pressing and holding the BLT/
REC button for 5 seconds. OFF will appear in the display and then you can release the button.
R
NOTE: Powering OFF the manifold will also turn off the recording mode.
DELETING RECORDED DATA
NOTE: When the delete recorded data command is performed all data will be erased from the
manifold.
NOTE: The data will not delete if you are in recording mode. Exit record mode in order to delete
the data.
• Once the data in the manifold is no longer of use delete the data by simultaneously holding
down the ENTER + BLT/REC buttons and then pressing the POWER button until the default
screen appears on the LCD.
CLEANING THE SENSOR
Observe the gasket after each vacuum. If oil is present, it is possible that there is a presence of
oil in the sensor chamber.
Follow these instructions:
1. Disconnect the sensor chamber from the socket.
2. Remove the gasket & depressor from the assembly to clean.
3. Clean the gasket. Rinse the sensor chamber with acetone. Repeat until the oil is completely
removed. Allow 2 – 4 hours for all of the parts to dry.
4. Reassemble all of the parts and check the unit.
FIG. D
DEPRESSOR
GASKET
1/4" FL-F Swivel Nut
PARTS AND ACCESSORY LIST
42010
42014
85511
99103-SENSOR
99903-BLOCK
99903-PC
99903-PB
99903-RB
98061-SENSOR
98062-001
99332
99903-USB
OPTIONAL ACCESSORIES
52232
52336
52337
98062
98210-A
99333
99334-110
99334-220

WARRANTY

This product warrants against defects in material and workmanship for a period of one year.
This warranty does not cover failure due to abuse, improper usage, or progressive wear and tear.
Warranty becomes valid to the original user, effective on the purchase date. A copy of an invoice
along with a registration card must be sent to 1 Aspen Drive, Randolph, NJ 07869 to validate the
warranty.
For further service please contact (973) 252-9119.
(SEE FIG. D)
SENSOR CHAMBER
SENSOR TUBE
Gasket for 1/4" FL
Depressor
3/8" Gasket for Black Hose
Sensor
Block for 99903
PC Board for 99903
Plastic Box
Rubber Boot
Sensor Assembly
Vacuum Sensor Cable (only)
1/8 NPT x 1/4 F Flare Swivel Adapter
USB Cable
Humidity Temperature Meter
Clamp-On Thermocouple (3 ft)
Clamp-On Thermocouple (10 ft)
Complete Vacuum Sensor & Cable Assembly
Accu-Charge II Electronic Refrigerant Scale
1/4 FL-M x 1/4 FL-M x 1/4 FL-F Tee
110V AC/DC Adapter
220V AC/DC Adapter (schuko plug)
www.mastercool.com
SOCKET
CABLE