All of the conditions below must be met!:
1.
The device is in error! (No AC output)
2.
Inverter LED flashes (in opposition to any flashing of the Bulk, Absorption or Float LED)
3.
At least one of the LEDs Bulk, Absorption and Float is on or flashing
Bulk LED off
Absorption LED
of f
f lashing
of f
0
3
f lashing
1
4
on
2
5
Bulk LED
Absorption LED
Code
Float LED
Dev ice is switched of f because one of
1
the other phases in the sy stem has
Not all, or more than, the expected
3
dev ices were f ound in the sy stem.
4
No other dev ice whatsoev er detected.
5
Sy stem time sy nchronisation problem
10
14
Dev ice cannot transmit data.
One of the dev ices has assumed
17
'master' status because the original
18
22
This dev ice cannot f unction as 'slav e'.
24
Switch-ov er sy stem protection initiated.
Firmware incompatibility . The f irmware
of one the connected dev ices is not
25
suf f iciently up to date to operate in
26
Bulk LED flashes
Absorption LED
On
of f
6
of f
9
7
f lashing
10
8
on
11
Meaning:
switched of f .
Ov erv oltage on AC-out.
occurred.
master f ailed.
Ov erv oltage has occurred.
conjunction with this dev ice.
Internal error.
f lashing
on
12
15
13
16
14
17
Cause/solution:
Check the f ailing phase.
The sy stem is not properly conf igured. Reconf igure the sy stem.
Communication cable error. Check the cables and switch all equipment of f ,
and then on again.
Check the communication cables.
Check the AC cables.
Should not occur in correctly installed equipment. Check the communication
cables.
Check the communication cables (there may be a short circuit).
Check the f ailing unit. Check the communication cables.
Check AC cables.
This dev ice is an obsolete and unsuitable model. It should be replaced.
Should not occur in correctly installed equipment. Switch all equipment of f ,
and then on again. If the problem recurs, check the installation.
Possible solution: increase lower limit of AC input voltage to 210VAC
(factory setting is 180VAC)
1) Switch all equipment of f .
2) Switch the dev ice returning this error message on.
3) Switch on all other dev ices one by one until the error message reoccurs.
4) Update the f irmware in the last dev ice that was switched on.
Should not occur. Switch all equipment of f , and then on again. Contact
Victron Energy if the problem persists.
Bulk LED on
Absorption LED
of f
f lashing
on
of f
18
21
24
f lashing
19
22
25
on
20
23
26
25