Herunterladen Inhalt Inhalt Diese Seite drucken

Victron energy MultiPlus 12/3000/120 Anleitung Seite 22

Vorschau ausblenden Andere Handbücher für MultiPlus 12/3000/120:
Inhaltsverzeichnis

Werbung

Verfügbare Sprachen
  • DE

Verfügbare Sprachen

  • DEUTSCH, seite 83
Parallel operation (appendix C)
Step 1: Setting ds2 and ds1 for parallel operation
Master
DS-8 AC input
Set
DS-7 AC input
Set
DS-6 AC input
Set
DS-5 AES
na
DS-4 Ch. current Set
DS-3 Ch. current Set
DS-2 Master
of f
DS-1 Master
on
The current settings (AC current limitation and charging current) are multiplied by the number of devices. How ever, the AC current limit
setting w hen using a remote panel w ill alw ays correspond to the value indicated on the panel and is not multiplied by the number of
devices.
Exam ple: 9kVA parallel system
-
If an AC input current limit of 20A is set on the master and the system consists of three devices, then the effective system
current limit w ill be equal to 3 x 20 = 60A (maximum input pow er 3 x20 x 230 = 13,8kVA).
-
If a 30A panel is connected to the master, the system current limit is adjustable to a maximum of 30A, regardless of the
number of devices.
-
If the charging current on the master is set to 100% (70A for a Multi 24/3000/70) and the system consists of three devices,
then the effective system charging current is equal to 3 x 70 = 210A.
The settings according to this example (9kVA parallel system w ith 30A Multi Control Panel) are as follow s:
Master
DS-8 na (30A panel)
DS-7 na (30A panel)
DS-6 na (30A panel)
DS-5 AES na
DS-4 Ch. current 3x70A
on
DS-3 Ch. current 3x70A
on
DS-2 Master
DS-1 Master
on
To store the settings after the required values have been set: press the 'Up' button of the m aster for 2 seconds (upper button to the
right of the DIP sw itches, see appendix A, position J). The overload and low-battery LED's w ill flash to indicate acceptance of the
settings.
We recommend making a note of the settings, and filing this information in a safe place.
The DIP sw itches can now be used to apply the remaining settings (step 2).
18
Slave 1
DS-8 na
DS-7 na
DS-6 na
DS-5 na
DS-4 na
DS-3 na
DS-2 Slav e 1
of f
DS-1 Slav e 1
of f
Slave 1
DS-8 na
DS-7 na
DS-6 na
DS-5 na
DS-4 na
DS-3 na
of f
DS-2 Slav e 1
of f
DS-1 Slav e 1
of f
Slave 2 (optional)
DS-8 na
DS-7 na
DS-6 na
DS-5 na
DS-4 na
DS-3 na
DS-2 Slav e 2
of f
DS-1 Slav e 2
on
Slave 2
DS-8 na
DS-7 na
DS-6 na
DS-5 na
DS-4 na
DS-3 na
DS-2 Slav e 2
of f
DS-1 Slav e 2
on

Quicklinks ausblenden:

Werbung

Inhaltsverzeichnis
loading

Diese Anleitung auch für:

Multiplus 24/3000/70Multiplus 48/3000/35

Inhaltsverzeichnis