Herunterladen Inhalt Inhalt Diese Seite drucken

Victron energy MultiPlus 12/3000/120 Anleitung Seite 12

Vorschau ausblenden Andere Handbücher für MultiPlus 12/3000/120:
Inhaltsverzeichnis

Werbung

Verfügbare Sprachen
  • DE

Verfügbare Sprachen

  • DEUTSCH, seite 83
4. Installation
This product may only be installed by a qualified electrical engineer.
4.1 Location
The product must be installed in a dry and w ell-ventilated area, as close as possible to the batteries. There should be a clear space of at
least 10 cm around the appliance for cooling.
Excessively high ambient temperature w ill result in the follow ing:
Reduced service life.
Reduced charging current.
Reduced peak capacity, or shutdown of the inverter.
Never position the appliance directly above the batteries.
The MultiPlus is suitable for w all mounting. For mounting purposes, a hook and tw o holes are provided at the back of the casing (see
appendix G). The device can be fitted either horizontally or vertically. For optimal cooling, vertical fitting is preferred.
The interior of the product must remain accessible after installation.
Try and keep the distance betw een the product and the battery to a minimum in order to minimize cable voltage losses.
For safety purposes, this product should be installed in a heat-resistant
environment. You should prevent the presence of e.g. chemicals, synthetic
components, curtains or other textiles, etc., in the immediate vicinity.
4.2 Connection of battery cables
In order to utilize the full capacity of the product, batteries w ith sufficient capacity and battery cables with sufficient cross section should
be used. See table.
Recommended battery capacity (Ah)
Recommended DC fuse
Recommended cross section (mm
per + and - connection terminal
0 – 5 m
5 – 10 m
* '2x' means tw o positive and tw o negative cables.
Remark: Internal resistance is the important factor w hen working with low capacity batteries. Please consult your supplier or the relevant
sections of our book "Energy Unlimited", dow nloadable from our w ebsite.
Procedure
Proceed as follow s to connect the battery cables:
Use an insulated box spanner in order to avoid shorting the battery.
Avoid shorting the battery cables.
Undo the four screws at the front of the enclosure and remove the front panel.
Connect the battery cables: see Appendix A.
Tighten the nuts w ell for minimal contact resistance.
8
12/3000/120
24/3000/70
400–1200
200–700
400A
300A
2
)
2
2x 50 mm
50 mm
2
2x 70 mm
2x 50 mm
48/3000/35
100–400
125A
2
2
35 mm
2
2
2x 35 mm

Quicklinks ausblenden:

Werbung

Inhaltsverzeichnis
loading

Diese Anleitung auch für:

Multiplus 24/3000/70Multiplus 48/3000/35

Inhaltsverzeichnis