4.4 Optional Connections

A number of optional connections are possible:
4.4.1 Second Battery
The MultiPlus has a connection for charging a starter battery. For connection see Appendix A.
4.4.2 Voltage Sense
For compensating possible cable losses during charging, tw o sense wires can be connected with which the voltage directly on the
battery or on the positive and negative distribution points can be measured. Use w ire w ith a cross-section of 0,75mm².
During battery charging, the MultiPlus w ill compensate the voltage drop over the DC cables up to a maximum of 1 Volt (i.e. 1V over the
positive connection and 1V over the negative connection). If the voltage drop threatens to become larger than 1V, the charging current
is limited in such a w ay that the voltage drop remains limited to 1V.
4.4.3 Tem perature Sensor
The temperature sensor supplied w ith the product may be used for temperature-compensated charging (see Appendix A). The sensor is
isolated and must be mounted on the batteries minus pole.
4.4.4 Rem ote Control
The product can be remotely controlled in tw o w ays.
With an external sw itch (connection terminal H, see appendix A). Operates only if the sw itch on the MultiPlus is set to "on".
With a Multi Control panel (connected to one of the tw o RJ48 sockets B, see appendix A). Operates only if the sw itch on the
MultiPlus is set to "on".
Only one remote control can be connected, i.e. either a switch or a Multi control panel.
4.4.5. Programmable relay
The MultiPlus is equipped w ith a programmable relay that by default is set as an alarm relay (connection terminal I, see appendix A).
The relay can be programmed for all kinds of other applications how ever, for example to start a generator (VEConfigure software
needed).
4.4.6 Auxiliary AC output (AC-out-2)
Besides the usual uninterruptable output, a second output (AC-out-2) is available that disconnects its load in the event of battery
operation. Example: an electric boiler or air conditioner that is allow ed to operate only if the genset is running or shore pow er is
available.
In case of battery operation, AC-out-2 is sw itched off immediately. After the AC supply has become available, AC-out-2 is reconnected
w ith a delay of 2 minutes, this to allow a genset to stabilise prior to connecting a heavy load.
4.4.7 Parallel Connection
The MultiPlus can be connected in parallel w ith several identical devices. To this end, a connection is established betw een the devices
by means of standard RJ45 UTP cables. The system (one or more Multis plus optional control panel) w ill require subsequent
configuration (see Section 5).
In the event of connecting MultiPlus units in parallel, the follow ing requirements must be met:
A maximum of six units connected in parallel.
Only identical dev ices may be connected in parallel.
The DC connection cables to the dev ices must be of equal length and cross-section.
If a positiv e and a negativ e DC distribution point is used, the cross-section of the connection between the batteries and the DC distribution point must
at least equal the sum of the required cross-sections of the connections between the distribution point and the MultiPlus units.
Place the MultiPlus units close to each other, but allow at least 10 cm f or v entilation purposes under, abov e and beside the units.
UTP cables must be connected directly f rom one unit to the other (and to the remote panel). Connection/splitter boxes are not permitted.
A battery -temperature sensor need only be connected to one unit in the sy stem. If the temperature of sev eral batteries is to be measured, y ou can
also connect the sensors of other MultiPlus units in the sy stem (with a maximum of one sensor per MultiPlus). Temperature compensation during
battery charging responds to the sensor indicating the highest temperature.
Voltage sensing must be connected to the master (see Section 5.5.1.4).
Only one remote control means (panel or switch) can be connected to the system.
4.4.8 Three-phase operation
The MultiPlus can also be used in 3-phase configuration. To this end, a connection betw een the devices is made by means of standard
RJ45 UTP cables (the same as for parallel operation). The system (Multis plus an optional control panel) w ill require subsequently
configuration (see Section 5).
Pre-requisites: see Section 4.4.7.