Herunterladen Inhalt Inhalt Diese Seite drucken

Making The Electrical Connection - WIKA MG-1 Betriebsanleitung

Vorschau ausblenden Andere Handbücher für MG-1:
Inhaltsverzeichnis

Werbung

Verfügbare Sprachen

Verfügbare Sprachen

6. Commissioning, operation
Types of sealing
per EN 837
GB

Making the electrical connection

Ground the pressure transmitter via the process connection.
This is Protection Class 3 equipment for connection at low voltages, which are separated from
the power supply or voltage by greater than AC 50 V or DC 120 V. Preferably, a connection
to an SELV or PELV circuit is recommended; alternatively protective measures from
HD 60346-4-41 (DIN VDE 0100-410).
Option for North America: The connection can be made in line with "Class 2 Circuits"
or "Class 2 Power Units" in accordance with CEC (Canadian Electrical Code) or
NEC (National Electrical Code).
Select a cable diameter that matches the cable gland of the plug. Make sure that the cable
gland of the mounted plug has a tight fit. To guarantee the ingress protection, tighten the gland.
For cable outlets, make sure that no moisture enters at the cable end.
14
per DIN 3852-E
WIKA operating instructions pressure transmitter, model MG-1
NPT, R and PT
Self-sealing thread typ

Werbung

Inhaltsverzeichnis
loading

Inhaltsverzeichnis