5.3.2 VE.Bus System Configurator and dongle
For configuring advanced applications and/or systems with four or more Inverters,
VE.Bus System Configurator software must be used. You can download the
software at www.victronenergy.com . VEConfigureII forms part of this program.
You can configure the system without a dongle, and use it for 15 minutes (as a
demonstration facility). For permanent use, a dongle – available at additional charge –
is required.
For connection to your computer, a RJ45 UTP cable and the MK2.2b RS485-to-
RS232 interface is required.
If your computer does not have a RS232 connection but is equipped with USB, you
will also need a RS232-to-USB interface cable.
Both are available from Victron Energy.
5.4 Implementing settings with a VE.Net panel
To this end, a VE.Net panel and the VE.Net to VE.Bus converter is required.
With VE.Net you can set all parameters, with the exception of the multi-functional relay
and the VirtualSwitch.
5.5 Configuration with DIP switches
A number of settings can be changed using DIP switches (see appendix A, position I).
Procedure:
Turn the Inverter on, preferably unloaded.
Set the DIP switches for:
AES (Automatic Economy Switch)
o
Inverter voltage
o
Inverter frequency
o
selection of stand-alone, parallel or 3-phase operation.
o
To store the settings after the required values have been set: press the 'Up'
button for 2 seconds (upper button to the right of the DIP switches, see
appendix A, position J).
Remarks:
- Dipswitches ds8,ds7 and ds6 are not assigned and should remain off.
- The DIP switch functions are described in 'top to bottom' order. Since the uppermost
DIP switch has the highest number (8), descriptions start with the switch numbered 5.
- In parallel mode or 3-phase mode, not all devices require all settings to be made
(see section 5.5.4).
- For parallel or 3-phase mode, read the whole setting procedure and make a note of
the required DIP switch settings before actually implementing them.
- The 'down' button is not used in this procedure and must not be pressed!
13