6.1.6 Elimination of Faults

Frage
Upon commissioning,
an inappropriate
language was chosen.
How can I find my
language?
Fault message 101
"Sensor fault does not
permit
acknowledgement."

6.1.7 Fault Messages and Their Reporting

The following are available as potential-free change-over contacts for fault messaging:
- Fault message P-min
- Fault message Control
- Fault message Pump 1
- Fault message Pump 2
- Batch fault message
When connected to any central control technology, it is possible to transmit fault messages as a binary signal to a
SICLIMATX.
6.2

Humidity Calculator

The hygrostat which comes with the CoolTrans, loosely packaged as a separate unit, serves to determine
ambient humidity at the place of installation.
For this purpose, a connection line of 5 x 1.5 mm² needs to be laid to the humidity calculator.
CoolTrans 50
Antwort
1. Press "ESC" and "OK" simultaneously
2. Select password level and enter 112 as a password
and confirm it by pressing "OK". Language will change
to English.
3. Change to your language in the menu "Settings > Device
> Language".
Password level (only service personnel)
Upon exiting the menu "Commissioning", it will be checked
as to which sensors are connected.
Should, at a later time, one of the sensors as were initially
reported connected detected to be missing, a fault message
will be generated.
Should a sensor have been wired wrongly and later, during
operation, have been re-wired, a "false" fault message may
be generated.
Elimination:
Return to the menu "Commissioning " (Caution! System is
put on hold!), then back to the main menu (Caution! System
re-starts!).
(for detecting water losses in the cooling water system)
Do not install in recesses or behind curtains.
Avoid direct sunlight.
Installation instructions are printed on the device wrapping.