CoolTrans 50 kW
Manual / Bedienungsanleitung
5.
Cross-referencing the supply circuits
Current throughput
readable on a scale in
l/min
Fig.: Flow distributor 5 x Tacosetter 3/4" female thread
The setting valves (Taco setter with display) help to adjust the cooling water volume flows as required
at the place of consumption and to be corss-referenced with each other. To be set by means of a
spanner at the square end.
5.1
Default Settings
The CTU is shipped with the following settings that are relevant to the user:
Pump change-over:
Desired temperature, secondary flow:
Time change to CET Daylight Saving Time:
Time change to CET Standard Time:
Admission pressure
at membrane extension tank:
Triggering pressure for minimal pressure relief:
CoolTrans 50
Setting the volume flow at
each cooling circuit
Mondays at 10:00 hrs
12°C (without moisture shift)
25 March, at 02:00 hrs
25 October, at 03:00 hrs
1.0 bar
0.5 bar (Level 1 / disturbance)
0.2 bar (Level 2 / unit shut off)
01.998.360.0 / Ausgabe -
page / Seite16/73