6.1.2 Control Settings

Upon initial commissioning, the control will report a fault message. In order to remove it, the clock time
and the date have to be set.
Setting the time / date
Main menu > time / date
Operational line
Time
Date
Year
Central European Daylight Saving Time automatically changes to Central European Standard Time. (see
Default Settings)
Language selection
Each type of device has been loaded with several languages.
Upon switching on the CoolTrans for the first time, it will use German. Languages may also be
changed during operation.
Selecting a language
Main menu > setting > device >
Operational line
Sprache
Setting the flow temperature
Main menu > service level > control unit 1> scheduled values
Operational line
Pre´ komf Soll oben
Komf Soll oben
Komf Soll unten
Pre´ komf Soll unten
First set "Pre` komf Soll oben" and "Pre` komf Soll unten" for the desired cooling water flow temperature,
then set "Komf Soll oben" and "Komf Soll unten" for the desired temperature. All four values need to equal
each other.
CoolTrans 50
Range
0:00 .... 24:00
01.01 .. 31.12
(Day; Month)
2000 ... 2080
Range
de
Range
01.998.360.0 / Ausgabe -
Default setting
00:00
01.01
2000
Default setting
Deutsch
Default setting
12°C
12°C
12°C
12°C
page / Seite20/73