3.3.3
Changing configured connection parameters
Requirement
The "IP Adaption" dialog is open, see chapter "Opening the 'IP Adaptation' dialog (Page 17)".
Procedure
20
1. Select the "Override projected connection
information" option in the "IP-Adaptation" dialog.
2. Click "Next" to open the "Specify Connection
address" dialog.
The "Connection List" includes the names of all
available connection parameters in the
WinCC (TIA Portal) project.
3. Select a connection.
4. Click "Edit connection" to open the dialog for
changing the connection parameters.
5. Select the "Override connection parameters"
check box.
The connection parameters are only overwritten
when the "Override connection parameters"
check box is selected. The connection
parameters are unchanged if the check box is not
selected.
6. Change the IP address.
7. Use "Apply" to save the new connection
parameters.
The "Connection Info" information box shows that
the parameters of the selected connection have
been overwritten.
Expansions with WinCC V12 (TIA Portal)
A5E32030248-AB, 07/2013