Baumer NE134 Betriebsanleitung Seite 38

Elektronischer vorwahlzähler
Vorschau ausblenden Andere Handbücher für NE134:

Werbung

Verfügbare Sprachen

Verfügbare Sprachen

NE134
Line 35
Line 36
Line 37
Line 38
Line 40
Line 41
Line 42
Line 50
38
Minimum pulse duration for control input 1
0 * 30 ms
1
100 µs
Function control input 2 (contact 10)
0
PC - Main counter - Reset static
1
PC - Main counter - Reset edge-triggered
2 * PC - Main counter - Stop
3
Hold
4
Programming disabled
5
Keylock
6
Print
7
Main counter-outputs ON
8
Main counter-outputs OFF
9
External counting input for batch counter
Function control input 3 (contact 11)
0 * tot - Totalizer - Reset static
1
tot - Totalizer - Reset edge-triggered
2
b - Batch counter - Reset static
3
b - Batch counter - Reset edge-triggered
4
Programming disabled
5
Keylock
6
Print
7
Main counter-outputs ON
8
Main counter-outputs OFF
9
External counting input for batch counter
Take-over of presets P1, P2, SC
0 * Effective immediately
1
When resetting
Output logic
0 * Both outputs as normally open
1
P1 normally closed, P2 normally open
2
P1 normally open, P2 normally closed
3
Both outputs as normally closed
Output time P1
0.01 s Minimum signal duration
* 0.25 s
99.99 s Maximum signal duration
Latch = Latched signal (by pressing the
Output time P2
0.01 s Minimum signal duration
* 0.25 s
99.99 s Maximum signal duration
Latch = Latched signal (by pressing the
Code setting
0 * Code not active
Max. 9999
www.baumer.com
- key)
- key)