Permissible medium temperature
Max. operating pressure of the pump
Sound pressure level
EMC (electromagnetic compatibility)
Emitted interference
Interference immunity
Motor protection
Fault current
1. Observe the manufacturer's specifications regarding mixing ratios. Add any additives to the medium to be pumped on the pressure side of the pump.
ATTENTION!
Danger of damage to property!
If impermissible media are pumped, the pump may be destroyed.
Permissible medium
Permissible max. ambient temperature
temperature
-10 °C ... +95 °C
-10 °C ... +90 °C
-10 °C ... +80 °C
-10 °C ... +70 °C
-10 °C ... +65 °C
Table 5.2:
Minimum inlet pressure (above atmospheric pressure) at the inlet
stub to prevent cavitation noise (with medium temperature T1)
Nominal width
Rp ½; Rp ¾; Rp 1; Rp 1¼
Table 5.3:
The values are valid up to 300 m above sea level; the values
above this height are higher: 0.01 bar/100 m added height.

5.3 Scope of supply

Pump, complete
Installation and operating instructions
2 x flat gasket
Coupling relay
EN-4
+ 40 °C
+ 50 °C
+ 55 °C
+ 60 °C
+ 65 °C
T
T
Med
Med
-10 °C...+50 °C
+95 °C
0.3 bar
1.0 bar
452115.66.16 · FD 9801
Tab. 5.2 on page 4
See type plate
< 35 dB(A)
General EMC: EN 61800-3
EN 61000-6-3, formerly EN 50081-1 (building standard)
EN 61000-6-2, formerly EN 50082-2 (industry standard)
Integrated motor protection as standard
3.5 mA
UPE 70-25 - UPE 120-32