Brief description of device
Brief description of device
3
3
Voltage measurement
Voltage measurement
6
6
The device is a multi-functional network
The device is a multi-functional network
analyser, which
analyser, which
The device has 4 voltage measurement inputs
The device has 4 voltage measurement inputs
• measures and monitors residual currents
• measures and monitors residual currents
and is suitable for various connection variants.
and is suitable for various connection variants.
tor
(RCM) and currents at the central grounding
(RCM) and currents at the central grounding
m
m
point (CGP). The residual current monitoring
point (CGP). The residual current monitoring
Danger of injury or damage to
Danger of injury or damage to
is carried out via an external residual current
is carried out via an external residual current
the device
the device
CAUTION!
CAUTION!
transformer (30 mA rated current) on the
transformer (30 mA rated current) on the
current measurement inputs I5 and I6.
current measurement inputs I5 and I6.
Disregard of the connection conditions for
Disregard of the connection conditions for
• measures and calculates electrical variables
• measures and calculates electrical variables
the voltage measurement inputs can result in
the voltage measurement inputs can result in
such as voltage, current, power, energy,
such as voltage, current, power, energy,
injuries or to the device being damaged.
injuries or to the device being damaged.
harmonics, etc. in building installations,
harmonics, etc. in building installations,
For this reason, note that:
For this reason, note that:
on distribution units, circuit breakers and
on distribution units, circuit breakers and
• Do not connect the voltage measurement
• Do not connect the voltage measurement
busbar trunking systems.
busbar trunking systems.
inputs
inputs
• displays and saves measurement results
• displays and saves measurement results
- to DC voltage.
- to DC voltage.
and transmits them via interfaces.
and transmits them via interfaces.
- Do not use for voltage measurement in
- Do not use for voltage measurement in
SELV circuits (safe extra low voltage).
SELV circuits (safe extra low voltage).
he
• Voltages that exceed the allowed network
• Voltages that exceed the allowed network
NOTE!
NOTE!
rated voltages be connected via a voltage
rated voltages be connected via a voltage
or
If residual currents in electrical systems
If residual currents in electrical systems
transformer.
transformer.
T
are monitored, the device (inputs I5/I6)
are monitored, the device (inputs I5/I6)
• The voltage measurement inputs are to
• The voltage measurement inputs are to
can trigger warning pulses if a response
can trigger warning pulses if a response
be equipped with a suitable, labelled fuse
be equipped with a suitable, labelled fuse
-
threshold is exceeded. The warning pulses
threshold is exceeded. The warning pulses
and isolation device located in the vicinity.
and isolation device located in the vicinity.
s.
can provide an alarm before a protective
can provide an alarm before a protective
• Measured voltages and measured
• Measured voltages and measured
device trips. The device does not provide
device trips. The device does not provide
currents must derive from the same
currents must derive from the same
protection against electric shock!
protection against electric shock!
network!
network!
L1
L1
L2
L2
NOTE!
NOTE!
NOTE!
NOTE!
L3
L3
L1
L1
For further information on device functions, data and assembly, see the user manual.
For further information on device functions, data and assembly, see the user manual.
A circuit breaker can be used as an alter-
A circuit breaker can be used as an alter-
N
N
L2
L2
L3
native to a fuse and isolating device.
L3
native to a fuse and isolating device.
N
N
V
V
V
V
3p 4w
1
3p 4w
2
1
3
V
V
V
V
V
V
V
V
V
V
Further connection variants for voltage measurement
3p 4w
Further connection variants for voltage measurement
1
3p 4w
2
1
3
2
4
3
ref
4
ref
8
8
Establish connection to the PC
Establish connection to the PC
12
12
Three-phase, four-conductor system
Three-phase, four-conductor system
The 3 most common connections for communication
The 3 most common connections for communication
between PC and device:
between PC and device:
L1
L1
L1
L1
L1
L1
L1
L2
L2
L2
L2
L2
L2
L2
L1
L3
L3
L1
L1
L3
L3
L3
L3
L3
1.
1.
Ethernet
Ethernet
L2
al
N
N
L2
N
PC
L2
N
PC
N
(crossover patch cable)
(crossover patch cable)
L3
L3
L3
N
The device and PC require a static IP address.
The device and PC require a static IP address.
6).
2.
2.
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
3p 4w
1
3p 4w
2
1
3
3p 4w
2
4
PC
3
ref
1
3p 4w
4
PC
2
ref
1
3
3p 3wu
2
4
3
ref
3p 3wu
1
3p 4wu
4
2
ref
1
3
3p 4w
V
V
V
V
V
V
V
V
V
V
3p 3wu
3p 3wu
1
2
1
3
2
4
3
ref
4
ref
Patch cabel
Patch cabel
Switch/
Switch/
3p 4w
3p 4w
Router
Router
ts
The device and PC require a static IP address.
The device and PC require a static IP address.
re.
Three-phase, three-conductor system
Three-phase, three-conductor system
L1
L1
L1
L1
L1
L1
L1
3.
3.
DHCP
DHCP
L2
L2
L2
L2
L2
L2
PC
L3
L3
L1
L1
server
L1
server
L3
L3
L3
L3
L2
L2
L2
L2
L3
L3
L3
Patch cabel
Patch cabel
Switch/
Switch/
Router
Router
DHCP server automatically assigns IP addresses to the device and PC.
DHCP server automatically assigns IP addresses to the device and PC.
V
V
V
V
3p 3w
1
3p 3w
2
1
3
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
3p 3wu
3p 3wu
1
2
1
3
3p 3wu
2
4
3
ref
3p 3wu
1
4
2
ref
1
3
2
4
3
ref
4
1p 2w
ref
V
V
V
V
V
V
V
V
V
V
3p 3w
3p 3w
3p 3wu
1
2
1
3
2
4
3
ref
4
ref
3p 3w
3p 3w
L1
L1
L1
L1
L
L2
L2
L2
L2
L
L1
L3
L3
L3
L3
L
Assembly
Assembly
Install the device in the weather-protected front
Install the device in the weather-protected front
panel of switch cabinets.
panel of switch cabinets.
L1
L2
L3
L1
N PE
L2
L3
N PE
Cut-out size:
138
Ensure!
Adequate ventilation
• The device is installed
Fuse
Fuse
(UL/IEC listed)
(UL/IEC listed)
Isolation device
Isolation device
• Observance of clearance
L1
L1
L2
L2
L3
L3
Fig. Installation situa-
N
N
tion, rear view
m
m
Damage to property due to
Damage to property due to
disregard of the installation
disregard of the installation
Fig. Connection example
instructions
instructions
CAUTION!
CAUTION!
"Voltage measurement".
V
V
V
V
V
V
V
V
V
V
3p 4w
1
3p 4w
2
1
3
2
4
3
ref
4
ref
3p 4wu
Disregard of the installation instructions can
Disregard of the installation instructions can
The voltage measurement inputs are designed for
The voltage measurement inputs are designed for
damage or destroy your device.
damage or destroy your device.
measurements in low voltage networks, that con-
measurements in low voltage networks, that con-
Ensure that you have enough air circulation
Ensure that you have enough air circulation
tain the following nominal voltages:
tain the following nominal voltages:
in your installation environment and in the
in your installation environment and in the
• According to IEC - 417 V phase to earth and
• According to IEC - 417 V phase to earth and
event of high environmental temperatures,
event of high environmental temperatures,
720 V phase to phase in 4-conductor systems.
720 V phase to phase in 4-conductor systems.
provide cooling if necessary.
provide cooling if necessary.
• According to UL - 347 V phase to earth and
• According to UL - 347 V phase to earth and
L1
L1
L1
L1
L2
600 V phase to phase in 4-conductor systems.
L2
600 V phase to phase in 4-conductor systems.
L2
L2
L3
L3
L1
L1
• 600 V phase to phase in 3-conductor systems.
• 600 V phase to phase in 3-conductor systems.
L3
L3
N
N
L2
L2
The rated voltages and surge voltages comply with
The rated voltages and surge voltages comply with
L3
L3
the overvoltage category 600 V CATIII.
the overvoltage category 600 V CATIII.
N
N
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
2
4
3
ref
4
ref
3p 4wu
3p 4wu
1
2
1
3
2
4
3
ref
4
V
V
V
V
V
V
V
V
V
V
3p 3wu
3p 3wu
1
2
1
3
2
4
3
ref
4
ref
1p 2w
V
V
V
V
V
V
V
V
V
V
3p 4wu
3p 4wu
1
2
1
3
2
4
3
ref
4
ref
Single-phase, three-conductor
Single-phase, three-conductor
system
system
L1
L1
L1
L1
L1
L1
L1
L1
L2
L2
L2
L2
L2
L2
L1
L1
L1
L3
L1
L3
L1
L3
L2
L2
L3
L3
L3
L2
L2
L2
N
UMG
N
UMG
N
N
L3
L3
L3
L2
L2
N
N
N
S1 S2 S1 S2 S1 S2 S1 S2
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
3p 4wu
1
2
4
2
3
ref
1
3
4
3p 4wu
3p 3w
2
4
ref
3
ref
3p 4wu
1
3p 3w
1
4
2
2
ref
1
3
1
3
1p 2w
2
4
2
4
3
ref
3
ref
1
1p 2w
4
4
2
ref
ref
1
3
2
4
3p 4w
3
ref
4
3p 5w
UMG
UMG
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
1
3p 4w
2
1
3
2
4
3
ref
4
ref
3p 4wu
3p 4wu
1
2
1
3
V
V
V
V
V
V
V
V
V
V
1p 2w
1
1p 2w
2
1
3
2
4
3
ref
4
ref
Patch cabel
Patch cabel
3p 4wu
3p 4wu
1p 2w
1p 2w
The device requires the mains frequency (range
The device requires the mains frequency (range
from 40 Hz to 70 Hz) for the measurement and
from 40 Hz to 70 Hz) for the measurement and
L
L
Ethernet connection
Ethernet connection
L1
L1
L1
L1
calculation of measured values.
calculation of measured values.
L
L
L2
PC
UMG
UMG
L1
L
L
L1
L1
L
L
L2
L2
L2
L3
L
L
L2
L
L
It is not necessary to confi gure a connection
It is not necessary to confi gure a connection
Patch cable
Patch cable
L3
N
N
L2
L2
L
L
schematic for measurement input V4!
schematic for measurement input V4!
Patch cabel
Patch cabel
L
L
m
m
N
N
Property damage due to
Property damage due to
incorrect network settings
incorrect network settings
CAUTION!
CAUTION!
S1 S2 S1 S2 S1 S2 S1 S2
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
2
4
3
ref
4
ref
3p 5w
1
3p 5w
2
1
3
2
4
3
ref
4
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
1p 2w
1
2
1
3
1p 2w
2
4
3
ref
1p 2w
1
4
2
ref
1
3
2
4
3
ref
4
ref
3p 2i0
Incorrect network settings can cause faults in
Incorrect network settings can cause faults in
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
3p 3wu
1
2
1
3
3p 5w
2
4
3
ref
3p 5w
4
ref
1p 2w
1
1p 2w
2
1
3
1
2
1
3
2
4
the IT network!
3
ref
4
the IT network!
ref
Find out the correct Ethernet network
Find out the correct Ethernet network
3p 3wu
3p 3wu
settings for your device from your network
settings for your device from your network
administrator.
administrator.
L
L
L
L
L
L
L
L
L1
L
L
L
L
L
L
Connecting the supply voltage
4
4
Schematic diagram for voltage measurement
7
7
The supply voltage level for your device is
specifi ed on the rating plate.
Voltage measurement in the three-phase,
After connecting the supply voltage, the fi rst
four-conductor system (TN, TT networks).
Cut-out size:
measured value indication "Home" appears
Note: Earth your system!
+0.8
138
x 138
+0.8
+0.8
x 138
mm
+0.8
mm
on the display. If no indication appears, check
whether the supply voltage is within the rated
Ensure!
voltage range.
Adequate ventilation
• The device is installed
vertically!
vertically!
• Observance of clearance
to adjacent components!
to adjacent components!
L1
L1
L1
L2
L2
L2
L3
Fig. Installation situa-
L3
L3
N
N
tion, rear view
Fig. Connection example
Grounding
the system
"Voltage measurement".
V
V
V
V
V
V
V
V
V
V
3p 4wu
1
2
1
3
2
4
3
ref
4
ref
3p 4w
Fig. Schematic diagram, device in a TN network.
L1
L1
L1
L1
L1
L2
L2
L2
L3
L3
L1
L1
L2
L2
L3
N
N
L2
L2
L3
L3
N
N
S1 S2 S1 S2 S1 S2 S1 S2
S1 S2 S1 S2 S1 S2 S1 S2
V
I
I
I
I
I
I
I
I
ref
3p 4w
1
3p 4w
2
1
3
2
4
3
4
V
V
V
V
V
V
V
V
V
V
1p 2w
1
2
1
3
2
4
3
ref
4
ref
3p 2i0
S1 S2 S1 S2 S1 S2 S1 S2
S1 S2 S1 S2 S1 S2 S1 S2
I
I
I
I
I
I
I
I
3p 4w
1
3p 4w
2
1
3
2
4
3
4
Current measurement
9
9
Controls and button functions
13
13
The device
Three-phase, fi ve-conductor
Three-phase, fi ve-conductor
• is intended for the connection of current
system
system
The device is operated via 6 function keys for the
• Selecting measured value indications.
L
L1
L
L1
L1
L1
L1
L1
L1
• Navigation within the menus.
L
L
L2
L2
L2
L2
L2
L2
L2
• does not measure DC.
L1
L1
L
L3
L
L1
L1
L3
L3
L3
L3
• Editing device settings.
L3
L3
L2
L2
The current measurement inputs can be loaded
L
L
N
L2
N
L2
N
N
N
L3
L3
N
N
L3
L3
Key
with max. 120 A for 1 second.
N
N
S1 S2 S1 S2 S1 S2 S1 S2
S1 S2 S1 S2 S1 S2 S1 S2
S1 S2 S1 S2 S1 S2 S1 S2
S1 S2 S1 S2 S1 S2 S1 S2
S1 S2 S1 S2 S1 S2 S1 S2
S1 S2 S1 S2 S1 S2 S1 S2
V
I
I
I
I
I
I
I
I
I
I
V
I
I
V
I
I
V
V
I
V
V
I
I
V
V
I
V
I
I
V
I
I
I
I
I
I
1
3p 4w
ref
2
3p 5w
1
1
3
2
3p 4w
2
4
1
3
3
2
4
1
3p 4w
4
3
ref
2
4
1
3
3p 2i0
ref
2
4
3
1
3p 2i0
4
2
1
3
3p 2i
2
4
3
1
3p 2i
4
3p 5w
2
S1 S2 S1 S2 S1 S2 S1 S2
S1 S2 S1 S2 S1 S2 S1 S2
S1 S2 S1 S2 S1 S2 S1 S2
S1 S2 S1 S2 S1 S2 S1 S2
V
V
V
V
V
I
I
I
I
I
2
4
3
ref
4
ref
3p 4w
1
3p 4w
2
1
3
2
I
I
I
I
I
I
I
I
3p 2i0
1
3p 2i0
2
1
3
2
4
3
4
3p 5w
3p 5w
L
L
L1
L1
L1
L1
L1
L
L
L2
L2
L2
L
L
L1
L1
Recommendation:
Recommendation:
L
L
L3
L3
L3
L2
L2
L
L
L
L
L2
L2
Use at least a CAT5
Use at least a CAT5
N
N
L3
L3
L
L
cable!
cable!
L
L
N
N
S1 S2 S1 S2 S1 S2 S1 S2
S1 S2 S1 S2 S1 S2 S1 S2
S1 S2 S1 S2 S1 S2 S1 S2
S1 S2 S1 S2 S1 S2 S1 S2
S1 S2 S1 S2 S1 S2 S1 S2
S1 S2 S1 S2 S1 S2 S1 S2
V
I
I
I
I
I
I
I
I
ref
3p 5w
1
3p 5w
2
1
3
2
4
3
4
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
1
3p 2i0
2
1
3
3p 2i0
2
4
3
1
3p 2i0
4
2
1
3
2
4
3
4
1p 2i
1
1p 2i
2
The current direction can be corrected via the
S1 S2 S1 S2 S1 S2 S1 S2
S1 S2 S1 S2 S1 S2 S1 S2
S1 S2 S1 S2 S1 S2 S1 S2
S1 S2 S1 S2 S1 S2 S1 S2
V
V
V
V
V
I
I
I
I
I
I
I
I
I
I
I
I
I
2
4
3
ref
4
3p 5w
ref
3p 5w
3p 2i0
1
3p 2i0
2
1
3
serial interfaces or on the device for each phase. If
2
1
2
1
3
2
4
3
4
incorrectly connected, a subsequent re-connection
of the current transformer is not required.
10 / 14
L
L
L
L
L
L
L
L
L
L
L
Connecting the supply voltage
Schematic diagram for voltage measurement
The supply voltage level for your device is
specifi ed on the rating plate.
Voltage measurement in the three-phase,
After connecting the supply voltage, the fi rst
four-conductor system (TN, TT networks).
measured value indication "Home" appears
Note: Earth your system!
on the display. If no indication appears, check
whether the supply voltage is within the rated
347V/600V 50/60Hz
347V/600V 50/60Hz
L1
L1
L1
L1
voltage range.
240V
240V
L2
L2
50/60Hz
50/60Hz
L3
L3
c
c
Danger of injury due to
Danger of injury due to
N
N
N
N
electrical voltage!
electrical voltage!
PE
PE
WARNING!
WARNING!
L1
L1
Serious bodily injury or death can result from
Serious bodily injury or death can result from
L2
L2
L3
L3
• Contact with bare or stripped live wires.
• Contact with bare or stripped live wires.
N
N
N
• Device inputs that are dangerous to touch.
• Device inputs that are dangerous to touch.
V4
V1
V4
V2
V1
V3
V2
Vref
V3
Vref
Render the system free of voltage before
Render the system free of voltage before
AC/DC
AC/DC
starting work! Check the system is free of
starting work! Check the system is free of
DC
DC
electrical energy!
Grounding
electrical energy!
the system
Voltage measurement
Voltage measurement
S1 S2 S1 S2 S1 S2 S1 S2
S1 S2 S1 S2 S1 S2 S1 S2
S1 S2 S1 S2 S1 S2 S1 S2
I
I
I
I
I
I
I
I
Auxiliary
Auxiliary
I
1
3p 4w
2
1
3
2
4
3
4
3p 2i
1
UMG 509-PRO
UMG 509-PRO
supply
supply
Fig. Schematic diagram, device in a TN network.
RECOMMENDATION!
RECOMMENDATION!
For a PE/N measurement, connect the
For a PE/N measurement, connect the
L1
L1
L1
L1
protective earth (PE) to measurement
protective earth (PE) to measurement
L2
L2
L2
input V4. Do not use a green/yellow
input V4. Do not use a green/yellow
L3
L3
L1
L1
L3
L2
N
N
L2
L2
wire for this as the conductor does not
wire for this as the conductor does not
L3
L3
have any protective function!
have any protective function!
N
N
S1 S2 S1 S2 S1 S2 S1 S2
S1 S2 S1 S2 S1 S2 S1 S2
S1 S2 S1 S2 S1 S2 S1 S2
S1 S2 S1 S2 S1 S2 S1 S2
S1 S2 S1 S2 S1 S2 S1 S2
I
I
I
I
I
I
I
I
3p 2i
1
3p 2i
2
1
3
2
4
3
4
I
I
I
I
I
I
I
I
I
1
3p 2i0
2
1
3
2
4
3
4
1p 2i
1
S1 S2 S1 S2 S1 S2 S1 S2
S1 S2 S1 S2 S1 S2 S1 S2
I
I
I
I
I
I
I
I
3p 2i
Current measurement
1
3p 2i
2
1
3
2
4
3
4
Controls and button functions
The device
• is intended for the connection of current
The device is operated via 6 function keys for the
transformers with secondary currents of
transformers with secondary currents of
• Selecting measured value indications.
L
L
L1
L1
../1 A and ../5 A.
L1
../1 A and ../5 A.
L1
• Navigation within the menus.
L
L
L2
L2
• does not measure DC.
L1
L1
L
L1
• Editing device settings.
L
L1
L2
L2
L3
L3
L2
L2
The current measurement inputs can be loaded
L
L
N
N
L3
L3
N
L2
Key
N
Function
L2
Function
with max. 120 A for 1 second.
N
N
c
c
• Back to home screen
• Back to home screen
Danger of injury due to
Danger of injury due to
• Exits selection menu
• Exits selection menu
electrical voltage!
electrical voltage!
S1 S2 S1 S2 S1 S2 S1 S2
S1 S2 S1 S2 S1 S2 S1 S2
S1 S2 S1 S2 S1 S2 S1 S2
S1 S2 S1 S2 S1 S2 S1 S2
S1 S2 S1 S2 S1 S2 S1 S2
S1 S2 S1 S2 S1 S2 S1 S2
S1 S2 S1 S2 S1 S2 S1 S2
WARNING!
WARNING!
• Select digit (to the left)
• Select digit (to the left)
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
1
3
1
3p 5w
3p 2i
2
4
2
3
1
1
3
3p 2i
4
2
2
4
1
3
3
1p 2i
2
4
4
3
1
1p 2i
4
2
1
3
2
4
3
4
S1 S2 S1 S2 S1 S2 S1 S2
S1 S2 S1 S2 S1 S2 S1 S2
Serious bodily injury or death can result from:
Serious bodily injury or death can result from:
• Selects main values (U, I, P ...)
• Selects main values (U, I, P ...)
S1 S2 S1 S2 S1 S2 S1 S2
S1 S2 S1 S2 S1 S2 S1 S2
I
I
I
I
I
I
I
I
I
I
4
3
4
3p 2i
1
3p 2i
2
1
3
2
4
3
I
I
I
I
I
I
I
I
1p 2i
1
1p 2i
2
1
3
2
4
3
4
• Contact with bare or stripped live wires.
• Contact with bare or stripped live wires.
• Changes (number -1)
• Changes (number -1)
• Current measurement inputs on the device
• Current measurement inputs on the device
• By-values (select)
• By-values (select)
and on the current transformer that are
and on the current transformer that are
• Selects menu item
• Selects menu item
dangerous to touch.
dangerous to touch.
• Changes (number +1)
• Changes (number +1)
Render the system free of voltage before
Render the system free of voltage before
L1
L1
• By-values (select)
• By-values (select)
starting work! Check the system is free of
starting work! Check the system is free of
• Selects menu item
• Selects menu item
electrical energy!
electrical energy!
L1
L1
L2
L2
Earth the system! Use the earth connection
Earth the system! Use the earth connection
• Select digit (to the right)
• Select digit (to the right)
L2
L2
points with earthing symbols for this!
points with earthing symbols for this!
• Selects main values (U, I, P ...)
• Selects main values (U, I, P ...)
Earth the secondary windings of current
Earth the secondary windings of current
transformers and all of the metal parts of
• Opens selection menu
transformers and all of the metal parts of
• Opens selection menu
the transformer that could be touched!
• Confi rm selection
the transformer that could be touched!
• Confi rm selection
S1 S2 S1 S2 S1 S2 S1 S2
S1 S2 S1 S2 S1 S2 S1 S2
S1 S2 S1 S2 S1 S2 S1 S2
I
I
I
I
I
I
I
I
I
I
I
I
I
I
1
3
2
1p 2i
4
3
1
1p 2i
4
2
1
3
2
4
3
4
The current direction can be corrected via the
NOTE!
NOTE!
S1 S2 S1 S2 S1 S2 S1 S2
S1 S2 S1 S2 S1 S2 S1 S2
I
I
I
I
I
I
I
I
I
I
4
3
serial interfaces or on the device for each phase. If
4
1p 2i
1
1p 2i
2
1
3
2
4
3
More detailed information on operation,
More detailed information on operation,
incorrectly connected, a subsequent re-connection
display and button functions for your device
display and button functions for your device
of the current transformer is not required.
can be found in the user manual.
can be found in the user manual.
Ground wire
Ground wire
Fuse
Fuse
Isolation device
Isolation device
connection
connection
Voltage measurement in the three-phase,
Voltage measurement in the three-phase,
three-conductor system (IT network).
three-conductor system (IT network).
The device is only suitable to a limited extent for
The device is only suitable to a limited extent for
use in IT networks, since the measured voltage
use in IT networks, since the measured voltage
relative to the housing potential is measured and
relative to the housing potential is measured and
the input impedance of the device creates residual
the input impedance of the device creates residual
current against the earth. The residual current can
current against the earth. The residual current can
Protective
Protective
conductor
conductor
trigger the insulation monitoring in IT networks.
trigger the insulation monitoring in IT networks.
Connection variants with voltage
Connection variants with voltage
transformers are suitable for IT networks
transformers are suitable for IT networks
L1
without restrictions!
without restrictions!
L2
L3
600V 50/60Hz
600V 50/60Hz
L1
L1
N
L2
L2
L3
L3
S1 S2 S1 S2 S1 S2 S1 S2
I
I
I
I
I
I
I
3p 2i
2
1
3
2
4
3
4
Impedance
Impedance
L1
L2
L1
L3
L2
N PE
L3
N PE
V4
V1
V4
V2
V1
V3
V2
Vref
V3
Vref
AC/DC
AC/DC
Fig. Connection of
Fig. Connection of
DC
DC
Grounding
Grounding
supply voltage.
supply voltage.
the system
the system
L1
Voltage measurement
Voltage measurement
Auxiliary
Auxiliary
UMG 509-PRO
UMG 509-PRO
L2
supply
supply
Fig. Schematic diagram, device in an IT network without N.
Fig. Schematic diagram, device in an IT network without N.
S1 S2 S1 S2 S1 S2 S1 S2
I
I
I
I
I
I
I
1p 2i
2
1
3
2
4
3
4
L1
L2
L1
L3
L2
N PE
L3
N PE
Fig. UMG 509-PRO display -
Fig. UMG 509-PRO display -
measured value indication "Home"
measured value indication "Home"
S
1
S
1
Display titles
Display titles
S
S
2
S
2
S
1
1
Measured
Measured
S
2
S
2
S
S
1
1
values
values
S
2
S
2
S
1
S
1
S
S
2
2
I
Labelling of the
Labelling of the
4
function keys
function keys
Function keys
Function keys
Fig. Example connection
Fig. Example connection
"Current measurement
"Current measurement
via current transformers".
NOTE!
via current transformers".
NOTE!
Current and voltage transformer ratios.
Current and voltage transformer ratios.
c
c
The current and voltage transformer ratios
The current and voltage transformer ratios
Risk of injury due to
Risk of injury due to
can be conveniently confi gured via
can be conveniently confi gured via
large currents and high
large currents and high
• the menu Confi guration >
• the menu Confi guration >
electric voltages!
electric voltages!
WARNING!
WARNING!
Measurement > Measurement
Measurement > Measurement
Current transformers that are operated open in the
Current transformers that are operated open in the
transformer > Phase L1.
transformer > Phase L1.
secondary side (high voltage peaks) can cause
secondary side (high voltage peaks) can cause
• the GridVis® software.
• the GridVis® software.
severe bodily injuries or death.
severe bodily injuries or death.
I
4
More details on current transformers
More details on current transformers
Avoid operating current transformers when open,
Avoid operating current transformers when open,
and voltage transformer ratios and their
and voltage transformer ratios and their
short circuit transformers that are unloaded!
short circuit transformers that are unloaded!
adjustment can be found in the user manual.
adjustment can be found in the user manual.
8
L1
L1
L2
L2
L3
L3
N
N
V
V
3p 4w
1
3p 4w
L1
L1
L2
L2
L3
L3
V
V
3p 3wu
3p 3wu
1
L1
L1
L2
L2
L3
L3
14
V
V
3p 3w
1
3p 3w