Operation With A Static Frequency Converter; Activation Types - Homa TP 28 Originalbetriebsanleitung

Vorschau ausblenden Andere Handbücher für TP 28:
Inhaltsverzeichnis

Werbung

Verfügbare Sprachen

Verfügbare Sprachen

Pump type
TP28 / TP30 / TP49
3Phase-Motor
TP pumps with 3Ph-motors are supplied with a separate
control box with motor starter, available from the HOMA
accessory program. If any other than an original control
unit is used, make sure that the thermal relay in the motor
starter is set according to the nominal current consump-
tion of the pump motor (see data on pump label).

5.9. Operation with a static frequency converter

The following points must be observed when operating
the converter:
The pump is suitable for operation with the frequency
converter according to DIN EN 60034-17.
Voltage peaks at the motor winding must be avoided
and, where appropriate, suitable filters must be pro-
vided in the motor lead.
The proper grounding of the entire system must be
ensured.
The specifications of the frequency converter manu-
facturer must be observed.
Under certain circumstances, a shielded cable is nec-
essary to comply with EMC directives.
The information sheet "Using HOMA pumps with the
frequency converter" must be observed.
Minimum speed for submersible pumps (wet-well pumps)
For submersible pumps a minimum speed is not required.
Take care that the pump, especial at lower speed, will
work hitch and vibration free. Otherwise the mechani-
cal seals might be damaged and untight. In addition, the
minimum flow velocity of 0.7 m/s must always be met or
exceeded.

5.10. Activation types

Activation types for cables with free ends (without
plugs)
Direct activation
Motor protection should be set to the rated current when
fully loaded. At partial load, we recommend that motor
protection is set 5% above the measured current at the
operating point.
Star-delta activation
If the motor protection is installed in the line:
Set the motor protection to 0.58 x the rated current. The
maximum start-up time in star-delta mode is 3 seconds.
If the motor protection is not installed in the line, set the
motor protection to the rated current when fully loaded.
Starting transformer/soft start
Motor protection should be set to the rated current when
fully loaded. At partial load, we recommend that motor
protection is set 5% above the measured current at the
operating point. The maximum start-up time at reduced
voltage (approx. 70%) is 3 seconds.
Operating capacitor
115 V
230 V
80 µF
25 µF
Operation with frequency transformers
The machine can be operated on frequency transformers.
Observe chapter 5.9 of this manual.
Activation types with plugs / relays
Connect the plug to the socket provided and press the
On/Off switch on the relay
5.10.1. After Start-Up
The rated current is briefly exceeded during the start-up
procedure. Once this process has ended, the operating
current should no longer exceed the rated current.
If the motor does not start immediately after the machine
is switched on, it must be switched off immediately. The
start pauses specified in the technical data must be ad-
hered to before starting up again. If the fault recurs, the
machine must be switched off again immediately. The
machine may only be started again once the fault has
been rectified.
The following items should be monitored:
Operating voltage (permissible deviation +/- 5% of
the rated voltage)
Frequency (permissible deviation -2% of the rated
frequency)
Current consumption (permissible deviation between
phases is a maximum of 5%)
Voltage difference between the individual phases
(max. 1%)
Starts and stops per hour (see technical data)
Air entry in the infeed, a deflector plate should be fit-
ted if necessary
Minimum water immersion level, level control unit,
dry-run protection
Smooth running
Check for leaks, if need be, follow the necessary
steps as set out in "Maintenance"
EngliSH | 47