Herunterladen Inhalt Inhalt Diese Seite drucken

Hydro Unit Installation - Toshiba HWS-803XWHT6-E Installationshandbuch

Hydro unit serie; hydrogerät; luft-wasser-wärmepumpe
Vorschau ausblenden Andere Handbücher für HWS-803XWHT6-E:
Inhaltsverzeichnis

Werbung

Verfügbare Sprachen

Verfügbare Sprachen

Hydro Unit
7
HYDRO UNIT
INSTALLATION
• To protect yourself from injury, always use PPE
(Personal Protective Equipment), that is, wear gloves.
• Install the Hydro Unit by at least two persons.
• Install the Hydro Unit in a place strong enough to
withstand the following weights:
Hydro Unit weight with no water 60 kg (802) 65 kg
(1402)
Hydro Unit weight with full water 80 kg (802) 85 kg
(1402)
• Do not install the unit in a place where water freezes.
• Do not install the Hydro Unit in a place where
combustible gas may leak.
• Do not install the Hydro Unit in a place exposed to rain
or water.
• Do not install the Hydro Unit near equipment which
generates heat.
• Do not install the Hydro Unit to a movable object.
• Do not install the Hydro Unit in a place exposed to
vibration.
„ Handling, Unpacking, and
Checking the Hydro Unit
• The unit should be checked when it is delivered, and
any damage reported immediately to the courier
claims the department.
11-EN
WARNING
CAUTION
„ Positioning
Service space
Secure a service space for the Hydro Unit.
• Do not install the Hydro Unit in a place where heat
stagnates.
▼ Fig. 7-01
200 mm
100 mm
500 mm
Mounting
Install M10 bolts at the positions shown below and
secure them with nuts.
▼ Fig. 7-02
380 mm
– 12 –
Installation Manual
500 mm
350 mm
M10
960 mm

Werbung

Inhaltsverzeichnis

Fehlerbehebung

loading

Inhaltsverzeichnis