Installation instructions

Installation on DIN rail (DIN EN 50022-35x7.5/15). The equipment must be installed vertically with the input terminals at the bottom and the output
terminals at the top, in order to ensure adequate heat dissipation. A clearance of at least 50 mm must be allowed above and below the device.
To snap the unit on to the DIN bar, hang it with its nose (A) into the bar (C) and press until the spring (B) snaps into place (see page 2). If
difficulty is experienced in snapping the unit on to the bar, loosen the spring (B) slightly as described under "Removing the Power Supply Unit".
To remove from the DIN bar, use a screw driver to loosen the spring (B) in the direction of the arrow.
The supply voltage (24 V DC) must be connected in accordance with VDE 0100 and VDE 0160. It is only allowed to be connected to a power
supply with "safe electrical isolation" in accordance with EN 60950.
!
Note: The 0 V connection (7) of the device merely serves to supply the internal electronic circuits. The 0 V of the loads must be supplied
directly to the power supply by means of separate lines.
Connections and terminal assignment
Terminals
Function
Input +24 V
+24 V input voltage connection (from
"+"
output of the power supply)
Input 0 V
0 V connection for supplying the
internal electronic circuits (from
output of the power supply)
Outputs
Outputs of the SDM module for
1, 2, 3, 4
connecting the load circuits
13, 14
Common signaling contact
Disconnection characteristic (typical):
Supply voltage > 20 V and the following power requirement for the branch concerned:
0 % to 100 % of setting
¡
101 % to 130 % of setting
¡
> 130 % of setting
¡
Supply voltage dip < 20 V and the following power requirement for the branch concerned:
> 100 % of setting
¡
Published by
Electronics Plant Vienna (EWW)
A&D Group
Siemensstraße 88-92
A 1210 Vienna
Siemens AG Österreich
Clamping range
0.33 to 10 mm
0.22 to 4 mm
"–"
0.22 to 4 mm
0.22 to 4 mm
No disconnection
¢
¢
Disconnection after approx. 5 s
¢
Current limited to approx. 130 %, disconnection after 50 to 100 ms
¢
Immediate disconnection
SITOP select
Seite 6 von 7
Remarks
2
Screw terminals; use a screwdriver with 5 mm blade width;
recommended tightening torque 1.2 Nm.
2
Screw terminals; use a screwdriver with 3.5 mm blade width;
recommended tightening torque 0.5 - 0.7 Nm.
Note: The 0 V of the loads must be supplied directly to the power
supply by means of separate lines !!
2
Screw terminals; use a screwdriver with 3.5 mm blade width;
recommended tightening torque 0.5 - 0.7 Nm.
2
Screw terminals; use a screwdriver with 3.5 mm blade width;
recommended tightening torque 0.5 - 0.7 Nm.
© Siemens AG Austria All rights reserved.
Subject to change without prior notice
Bestell-Nr.: C98130-A7524-A1-03-7419