Mounting and Connection Instructions - Ethernet-Interface 026840.29
5.2 Settings for TRSxx, ACSxx,
1. Select "1 Channel 1 configuration" and check the following parameters. If necessary set them
to the values as follow (confirm both, correct and changed values with "Enter)":
Baudrate (19200) ?
I/F Mode (78) ?
Flow (00) ?
Port No (10001) ?
ConnectMode (CO) ?
Send "+++" in Modem Mode (Y) ?
Auto increment source port (N) ?
Remote IP Address: (000) .(000) .(000) .(000)
Remote Port (0) ?
DisConnMode (00) ?
FlushMode (77) ?
DisConnTime (00:00) ?
SendChar 1 (00) ?
Send Char 2 (00) ?
Do not change all the remaining settings!
Wrong or incorrect entries - especially a wrong Netmask
configuration - can cause the access to this ethernet interface no
longer being possible. In that case the interface must be sent back
to the manufactorer.
2. Save settings and exit Telnet via "9 = Save and exit"
ACT
and external bus controller*
Baudrate: ACS-2/8 19200 or 38400
Port No.: = freely selectable,
(* not with MultiAccess Lite)
all other devices 19200
recommended value from
10001 on.
This port number can be
used for all controllers/
terminals.
Do
not
use the reserved
port numbers as follow:
1 - 1024
9999
14000 - 14009
30704
30718