User Manual SICLOCK DCF77 Reception Service for SIMATIC S7-300/400
3.3.2
10ms Cyclic Interrupt OB (OB35 or OB38)
In the 10ms Cyclic Interrupt organization block the function block FB77 must be
called with parameter Aufruf=0. For S7-416 and S7-417 OB38 is to be used,
otherwise OB35. Here the projected binary input must be given.
Note:
At S7-300, the Cyclic Interrupt is set by default at 100ms and must therefore be reset
to 10ms.
Figure 4: Call in the 10ms Cyclic Interrupt OB
Document order No.: 2XV9450-1AR33
Version 3.0
Page 13 of 17