Technical datas

The power supplies and electrical control equipment are to be operated exclusively with the components authorised
by the manufacturer
Execution:
Electrical properties
Operating voltage supply:
Permissible voltage range:
Permissible ripple voltage:
Current draw:
Cut-off "Open"
Cut-off "Close"
Power cut-off in each position:
Power consumption at cut-out torque:
Current still present after switching off:
Class of protection:
Mechanical properties
Stroke length:
Pressing force:
Tractive force:
Nominal clamping
force:
Side force / Shear force:
Speed:
min. Casement height at stroke length:
Dimensions (L x H x T):
Weight
Circuit connections and operation
Connection cable:
Electr. connection:
Connections:
Terminal connections:
Pause time during change of polarity:
Start-up time:
Opening / closing operation:
Timing according to prEN 12101-9:
Service life:
20
M2 500N
../EV1/..
../LA/EV1/..
-15 % / +25 % of nominal voltage
1,0 A
externally via
internally
power cut-off
externally via
internally
power cut-off
OPEN = 1,0 A, CLOSE = 1,0 A
Class III in accordance with DIN EN 61140 (VDE 0140-1)
200, 300, 500, 750 and 1000 mm
lengths between available
500 N
500 N
2000 N
depending on the installation location and the profiles.
To determine the value a configuration is necessary.
up stroke 750 mm =(stroke + 228 mm) x 60 x 41 mm
from stroke 750 mm =(stroke + 290 mm) x 60 x 41 mm
model stroke 1000 mm = ca. 4,5 kg
2 x 0,75 mm²
2 x 0,75 mm²
Connection cable, length about 2 m from cable channel end
(up to 10 m by special order)
see technical documentation
see technical documentation
30 % start-up time relating to 10 min, 3 min ON, 7 min OFF
Reversing the polarity of the operating voltage
suited, with change of direction
> 10.000 ventilation cycles at nominal load
M2 Tandem 500 N
../SG/EV1/..
../TD /LA/EV1/..
24 V DC
2 V
ss
integrated electronic power cut-
externally via
off and blockade
synchro modul
protective shutdown for the
opening process
integrated electronic power cut-
externally via
off and blockade
synchro modul
protective shutdown for the
opening process
yes
OPEN = 1,0 A, CLOSE = 1,0 A
200, 300 and 500 mm
lengths between available
not allowed
approx. 8,3 mm/s
(stroke + 228 mm) x 60 x
41 mm
2 x 1,5 mm² +
4 x 0,5 mm²
3 x 0,5 mm²
> = 100 ms
2 x 1,0 A
2 x 500 N
2 x 500 N
2 x 2000 N