Herunterladen Inhalt Inhalt Diese Seite drucken

Ul-Gerechte Installation; Power Terminals; Short Circuit Current Rating; Branch Circuit Protection - SEW-Eurodrive MOVIPRO-ADC Betriebsanleitung

Vorschau ausblenden Andere Handbücher für MOVIPRO-ADC:
Inhaltsverzeichnis

Werbung

7.4

UL-gerechte Installation

HINWEIS
Das folgende Kapitel wird unabhängig von der Sprache dieser Dokumentation auf-
grund von UL-Anforderungen immer in englischer Sprache abgedruckt.
7.4.1

Power terminals

Use 75 °C copper wire only.
7.4.2

Short circuit current rating

Max. voltage is limited to 500 V.
7.4.3

Branch circuit protection

Integral solid state short circuit protection does not provide branch circuit protection.
Branch circuit protection must be provided in accordance with the National Electrical
Code and any additional local codes.
For MOVIPRO
200 kA/500 V
When protected by:
Non Semiconduc-
tor Fuses (currents
Model
are maximum va-
PHC21A-
A022M1-...A-00/..
40 A/600 V
PHC21A-
A040M1-...A-00/..
40 A/600 V
PHC21A-
A075M1-...A-00/..
40 A/600 V
®
MOVIPRO
is suitable for use on a circuit capable of delivering not more than
200,000 rms symmetrical amperes when protected by fuses and circuit breakers
as described in the tables below.
®
MOVIPRO
is suitable for use on a circuit capable of delivering not more than
65,000 rms symmetrical amperes when protected by ABB and Rockwell Type E
Combination Motor controllers as described in the tables below.
®
use branch circuit protection as follows:
Three Phase 380 V – 500 V Voltage Range
SCCR:
SCCR:
200 kA/500 V
When protected by:
Inverse-Time Cir-
cuit Breaker
lues)
50 A max/500 V min
50 A max/500 V min
50 A max/500 V min
Elektrische Installation
UL-gerechte Installation
SCCR: 65 kA/480 V
SCCR: 65 kA/460 V
When protected
When protected by:
1)
by:
Type E Combinationen Motor Controller
Rockwell Automati-
ABB, Model
MS132‑6.3 Ra-
140M‑C2E-B63 Ra-
ted 480 V, 3 HP
ted 460 V, 5 HP
Rockwell Automati-
ABB, Model
MS132‑10 Ra-
140M‑C2E-C10 Ra-
ted 480 V, 5 HP
ted 460 V, 7.5 HP
Rockwell Automati-
ABB, Model
MS132‑16 Ra-
140M‑D8E-C16 Ra-
ted 480 V, 10 HP
ted 460 V, 10 HP
Betriebsanleitung – MOVIPRO
7
on, Model
on, Model
on, Model
59
®
-ADC