Connection and alarm by means of a fire alarm system (terminal
13/14)
Connection and alarm by means of a fire alarm system (terminal 13/14). At the effeff emergency
exit control terminal, it is additionally possible to connect the tripping contact of a fire alarm
system (fail unlocked loop). By tripping the fire alarm system, an alarm is given off at the control
terminal and the door is immediately unlocked.
Important note!
If there is no fire alarm contact connected at the control terminal, use a wire bridge to
connect terminals 13/14.
If the alarm has been tripped by a fire alarm system, the alarm must be acknowledged and reset
by the fire alarm system. At the control terminal, it is only possible to acknowledge the alarm.
The closed door is relocked after acknowledgement at the fire alarm system. If the door is
opened on acknowledgement at the fire alarm system, the temporary release time starts to
count down. If the door remains open, a pre-alarm or alarm is initiated.
The acoustic alarm by the fire alarm system can be suppressed in the control terminal by turning
the function key S 4.4 to the OFF position.
1.4.3

Sabotage alarm

The control terminal is fitted with a sabotage contact which signals when the device is opened
(by unauthorized persons). This is intended to prevent interference or manipulation at the
control terminal which would jeopardize operational safety. If the device is opened, an alarm is
initiated immediately irrespective of its locking status. This means that the floating "Alarm"
contact closes and the internal acoustic alarm transmitter is activated. This status is displayed by
the yellow LED. The door is not unlocked.
1.4.4

Alarm due to door break-in

If the door is broken open, an alarm is tripped immediately. This alarm is displayed by the red and
yellow LED as well as an internal acoustic signal transmitter. In addition, the floating "Alarm" relay
contact closes. This can be used to actuate external modules. In contrast to the danger alarm, in
this case the door is not unlocked. Alarm acknowledgement and reset correspond to the
procedure used with a danger alarm. Resetting the alarm by only closing the door is not possible.
1.4.5

Dealing with multiple alarms

If an alarm has been tripped, this can be acknowledged as described above. If the same alarm
condition occurs after acknowledgement, no additional alarm is triggered. This is only displayed
by the fact that the green LED starts to flash again at a ratio of 1:1. However, if a different alarm
condition occurs, a new alarm is tripped.