Herunterladen Inhalt Inhalt Diese Seite drucken

Notes; General Description - effeff 1338-14 Installationsanleitung

Vorschau ausblenden Andere Handbücher für 1338-14:
Inhaltsverzeichnis

Werbung

Verfügbare Sprachen

Verfügbare Sprachen

1.1 Notes

The relevant statutory building regulations must be observed when installing and operating
electrical locks in escape routes.
Agreement of the units with the "Directive on locking systems for doors in escape routes
(EltVTR 12/97)" (Building register A part 1, no. 6.19) has been tested by TÜV Rheinland,
Cologne

1.2 General description

The emergency exit control terminal type 1338/1340 is designed for the control and monitoring
of individual emergency exits. It accommodates the entire electronic control circuitry,
eliminating the need for an additional control unit. All relevant operating and control elements
are integrated in the control terminal and therefore do not need to be additionally externally
connected.
Does apply for models 1338-14/-15/-20/-21 or 1340-14/-15/-20/-21:
The following functions are available to you:
Stand-Alone-Mode. The control terminal take over the entire control and monitoring
of the escape door.
Release of the emergency exit via an integrated emergency button
External release of the emergency exit (for example by a fire alarm system)
Permanent unlocking using the internal key-operated switch or through an external
contact such as a time switch
Temporary unlocking via the internal key-operated switch or through an externally
connected button
Central release with alarm initiation via an external button
Display of the emergency exit locking status by means of the door status display
Display of an alarm status by means of an acoustic and optical signal
One floating relay contact each for an additional "locked-unlocked" display and for an
external alarm signal
Operation in combination with an external central panel type 725 or an operator
terminal 1332-10/11.
Does apply for models 1338-20/-21 und 1340-20/-21:
The models 1338-20/-21 and 1340-20/-21 have got two operation modes:
In operating mode 1, the control terminal operates as stand-alone unit. This means, that the
control terminal take over the entire control and monitoring of the escape door. The
operating have to take place at the control terminal or via an external operator terminal,
e.g. 1332.
In operating mode 2, the control terminal operates as bus user at door control bus. With the
additional central control panel 925, extended operating and monitoring possibilities are
available.