OVERLOAD TIMES
100% < Load
110% < Load
Load > 150%
(1)
@ nominal load, minimum voltage of 164 Vac, battery charging
(2)
@ nominal load, nominal voltage of 230 Vac, battery charging
(3)
Mains/Battery @ load 0% -100%
(4)
@ Mains/battery/mains @ resistive load 0% / 100% / 0%
(5)
If the mains frequency is within ± 5% of the value selected, the UPS is synchronized with the mains. If the frequency is
outside the tolerances or operation is battery-powered, the frequency is the selected frequency +0.1%
(6)
20 - 25 °C for longer battery life
(7)
To maintain the output voltage inside the precision range indicated, a recalibration may be necessary after a long period
in operation
(8)
Time required to reach 90% of the charge (after a full discharge)
(9)
Corresponding to: 19" x 4U x 26" (H x L x D)
Activates bypass after 2 sec
110%
Stoppage after 120 sec
Activates bypass after 2 sec
150%
Activates bypass instantaneously
T
OPERATION POWERED BY
BYPASS
Stoppage after 4 sec
Stoppage after 1 sec
ECHNICAL DATA TABLE
INVERTER
Stoppage after 60 sec
Stoppage after 4 sec
Stoppage after 0.5 sec
69