 Commands in progress: indicates presence of a remote command in progress.
CODE
C01
C02
C03
C04
LOCK
The LOCK (block) type report signals are usually preceded by an alarm signal and, on account of their
importance, result in the inverter being switched off and the load being powered through the bypass line (the
procedure is excluded in case of lockouts due to strong and persistent overloads and lockouts following a short-
circuit).
CODE
L03
L04
L05
L07
L10
L13
L20
L21
L40
L41
L42
L43
L50
L51
L52
L53
DESCRIPTION
Remote shutdown command
Remote load on bypass command
Remote switch-on command
Battery test in progress
DESCRIPTION
Auxiliary power supply incorrect
High temperature on heat sinks
Temperature Sensor1 broken
Temperature Sensor2 broken
Input fuse broken or input relay stuck (does not close)
Capacitor precharging failure
Capacitor bank undervoltage
Capacitor bank overvoltage
Inverter overvoltage
D-C voltage on output
Inverter voltage not right
Inverter undervoltage
Overload: load > 103%
Overload: load > 110%
Overload: load > 150%
Short-circuit