Herunterladen Inhalt Inhalt Diese Seite drucken

ECTIVE SI Series Montage- Und Betriebs-Anleitung Seite 51

Sinus/sine inerter
Inhaltsverzeichnis

Werbung

Verfügbare Sprachen

Verfügbare Sprachen

[
ECTIVE
SINUS/SINE INVERTER – SI-/TSI-SERIES
®
Caution!
The device remains switched on when the AC output is disconnected . There is a risk of
deep discharge of connected batteries due to the power consumption of this standby
mode .
The inverter disconnects the AC output in the following cases:
• internal temperature too high
• required output load too high
• input voltage too high or too low
Reason
risk of under­
10 .8V±0 .2V
voltage
total undervolt­
10 .2V±0 .2V
age
overvoltage
15 .5V±0 .2V
overheating
overload due
to powerful
consumers
12 V
24 V
21 .6V±0 .4V
20 .4V±0 .4V
31 .0V±0 .4V
internal temperature >75°C
regardless of the type
]
48 V
43 .2V±0 .8V
2x acoustic signal
+ red LED flashing 2x
every 8 sec .,
inverter still working
40 .8V±0 .8V
3x acoustic signal
+ red LED flashes 3x
every 8 sec .,
automatic shutdown
62 .0V±0 .8V
4x acoustic signal
+ red LED flashing 4x
every 8 sec .,
automatic shutdown
5x acoustic signal
+ red LED flashes 5x
every 8 sec .,
automatic shutdown
11x acoustic signal
+ red LED flashes con­
stantly until the error
is solved and device is
switched on again
Action