For the position of the REPO connector, see Figure 10.
Figure 12 shows a drawing of the REPO connectors.
You can set the REPO polarity. See the " REPO Input Polarity " setting
under User Settings.
Depending on the user configuration, the contacts must be
opened (recommendation) or closed to maintain the opera-
tion of the UPS system. To restart the UPS system, close the
REPO connection contacts (or open these again) and switch
the UPS system on manually. The maximum resistance in
the circuit amounts to 10 Ohm.
XS700-XS3000_manual_ger_eng_it_V1.1.0.doc
Figure 12: Emergency-off connection
NOTE
117 / 222