Herunterladen Inhalt Inhalt Diese Seite drucken

Analogue Outputs - Camille Bauer EURAX DME 424 Betriebsanleitung

Programmierbare multi-messumformer
Inhaltsverzeichnis

Werbung

Verfügbare Sprachen

Verfügbare Sprachen

Symbols
Meaning
PF
Active power factor cosϕ = P/S
PF1
Active power factor phase 1
PF2
Active power factor phase 2
PF3
Active power factor phase 3
QF
Reactive power factor sin ϕ = Q/S
QF1
Reactive power factor phase 1
QF2
Reactive power factor phase 2
QF3
Reactive power factor phase 3
LF
Power factor of the system
LF = sgnQ · (1 – PF)
LF1
Power factor phase 1
sgnQ1 · (1 – PF1)
LF2
Power factor phase 2
sgnQ2 · (1 – PF2)
LF3
Power factor phase 3
sgnQ3 · (1 – PF3)
c
Factor for the intrinsic error
R
Output load
Rn
Rated burden
H
Power supply
Hn
Rated value of the power supply
CT
c.t. ratio
VT
v.t. ratio
Input
Waveform:
Sinusoidal
Nominal frequency:
Acc. to type label
Consumption
(at external
power supply):
Voltage circuit: U
Current circuit: ≤ I
Continuous thermal ratings of inputs
Current circuit
10 A
Voltage circuit
480 V single-phase AC system
831 V three-phase system
34
P1/S1
P2/S2
P3/S3
Q1/S1
Q2/S2
Q3/S3
/ 400 kΩ
2
· 0.01 Ω
2
400 V
single-phase
AC system
693 V
three-phase system
Short-time thermal rating of inputs
Input
Number
variable
of inputs
Current
400 V single-phase AC system
circuit
693 V three-phase system
100 A
5
250 A
1
Voltage circuit 1 A, 2 A, 5 A
Single-
phase
AC system
600 V
H
: 1.5 Ur
10
intern
Three-phase
system
1040 V
H
: 1.5 Ur
10
intern

Analogue outputs

For the outputs A, B, C and D:
Output
Impressed
variable Y
DC current
Full scale Y2
see "Ordering
information"
Limits of
output signal
for input
overload
and/or
R = 0
1.25 · Y2
R→ ∞ 30 V
Rated useful
range of output
7.5 V
0 ≤
load
Y2
AC component
of output signal
≤ 0.005 · Y2
(peak-to-peak)
The outputs A, B, C and D may be either short or open-
circuited. They are electrically insulated from each other and
from all other circuits (floating).
Digital outputs, pulse outputs, limit outputs
The digital outputs conform to DIN 43 864. The pulse width
can be neither programmed nor is there a hardware set-
ting.
Type of contact:
Open Collector
Number of pulses:
Programmable
Duration
Interval
of
between two
overloads
overloads
3 s
5 min.
1 s
1 hour
10 s
10 s
10 s
10 s
Impressed
DC voltage
see "Ordering
information"
40 mA
1.25 · Y2
15 V
Y2
Y2
≤ ∞
Y2
2 mA
1 mA
≤ 0.005 · Y2

Werbung

Inhaltsverzeichnis
loading

Diese Anleitung auch für:

Eurax dme 442

Inhaltsverzeichnis