Safety distances

Note
Distance to non-combustible objects:
a > 40cm
b / c ≥ mounting dimensions
d ≥ 20cm if protrusion e = 0 till 20cm
d ≥ 30cm if protrusion e = 20 till 30cm
d ≥ 40cm if protrusion e > 30cm
Distance to combustible objects and reinforced concrete load-bearing walls:
a > 80cm
Mounting at combustible objects and reinforced concrete load-bearing walls
only in combination with heat shield option E15888!
b > 20cm
c > 120cm
d > 80cm
Lateral view:
e
d
a
10cm
Top view:
b
a
Distance in front of the stove:
c
b
b
b
Prior to set up
Floor bearing capacity
Ensure that the substructure is capable of bearing the weight of the stove prior
to set-up.
Note
No modifications may be made to the firing installation. This also leads to loss
of warranty and guarantee.
Floor protection
A base is required (glass, sheet steel or ceramic) if the floor is combustible
(wood, carpet, etc.).
Flue pipe connection
Flue pipes pose a particular source of hazard regarding gas leaks and
Q
fire. Get the advice of an authorised specialist company for the layout and
assembly.
Please observe the corresponding installation guidelines for walls panelled
Q
with wood when connecting your flue pipes to the stove,
Observe the formation of flue gas (atmospheric inversion) and draughts
Q
when the weather is unfavourable.
Infeed of too little combustion air can lead to smoke in the rooms or to flue
Q
gas leaks. Hazardous deposits in the stove and chimney may also occur.
If flue gas escapes, let the fire burn out and check whether all the air inlet
Q
openings are free and the flue gas pipes and the stove pipe are clean. If in
doubt notify the master chimney sweep since draught malfunctions may be
connected to your chimney.
Stoves type 1 (BA 1):
Suitable for multiple occupancy. (Note the different country regulations)
Q
These may only be operated with the combustion chamber door closed.
Q
The combustion chamber door is to be kept closed when the stove is not
Q
in operation.
Note
Your pellet stove has been tested as a room-air independent stove according
to EN14785. It can be operated room air dependent or optional room air
independent.
ROOM-AIR INDEPENDENT OPERATION:
The stove is certificated for type FC52x / FC62x of the approval principles for
the inspection and evaluation of ambient air independent fireplaces specified
by the Deutsches Institut für Bautechnik (DIBT) (German Institute for Building
Technology). Thanks to an air-tight configuration of the air supply line and flue
a
pipes the stove may be operated in air-tight rooms and in rooms with room-air
installations (e.g. controlled ventilation and venting systems, extractors etc.).
ROOM-AIR DEPENDENT OPERATION:
In combination with room-air installations (e.g. controlled ventilation and
venting systems (extractors etc.) it must be ensured that the stove and
the room air system are monitored and safeguarded mutually (e.g. via a
differential pressure controller). The combustion air infeed of approx.
20 m3/h must be ensured.
Please observe the respective local regulations and rules in consultation with
your master chimney sweep. For changes after the printing of this manual, we
can not assume any liability. We reserve the right to change without notice.