Like with an RCD, the currents between the outer cable(s) (L1, L2, L3) and the neutral con-
ductor (N) are compared using a converter. The difference is displayed.
The ground conductor leakage current must not exceed 3.5 mA during this measurement
**).
**) These requirements comply with DIN VDE 0701-0702 and ÖVE/ÖNORM E8701-1. Also
refer to the applicable requirements and standards in your country. Product standard
IEC62109-1:2010 is also applied to the Fronius Agilo. This product standard limits the
ground conductor leakage current to a maximum of 3.5 mA.
And finally...
-
-
-
-
-
-
-
126
Disconnect the inverter when not under load from the AC grid and DC supply
Check that the system is de-energised
Observe the discharge time
Re-attach all removed cables, DatCom components or earthing fuses (restore condi-
tion or inverter prior to repair or safety inspection)
Fit all missing housing components - all housing components, insulation components
and protective covers must be present and undamaged
Fit the air inlet grille using 5 TX25 screws - 3 Nm
Close the door