Herunterladen Diese Seite drucken

VEVOR CW-5200 Benutzerhandbuch Seite 13

Werbung

Verfügbare Sprachen
  • DE

Verfügbare Sprachen

  • DEUTSCH, seite 38
CODE
SET UP THE PROJECT
Set the temperature
F0
F1
Temperature difference value
F2
Refrigeration differential back
F3
Control mode
Water temperature super
F4
high alarm
Water temperature ultra-low
F5
alarm
F6
Alarm for high temperatures
F7
password
Maximum set
F8
water temperature
Minimum set
F9
water temperature
F10
Traffic 1 alarm value
F11
Traffic 2 alarm value
A0
Heating differential back
A1
Power-on alarm delay
A2
Power-on delay
A3
State transition delay
A4
Room temperature correction
A5
Water temperature correction
A6
System inertia coefficient
Compressor start-up
A7
protection
Temperature unit
A8
MENU DESCRIPTION
RANGE
F9~F8/-20~
40
– 15~5
0.1~3.0
0~1
1~20
1~20
40~50
00~99
(F9+1)~40
1~(F8-1)
0.0~10.0
0.0~10.0
0.1~3.0
0~30
10~99
0~99
﹣5.0~5.0
﹣5.0~5.0
2~30
0~99
0~1
- 12 -
DEFAULT
REMARK
VALUE
25.0
Smart temperature mode
Thermostatic mode
-2.0
0.3
Accuracy 0.1 degrees
1
1 Smart, 0 Thermostat
10.0
15.0
45.0
8
30.0
20.0
0.5
0.0 = Cancel alarm
0.0
0.0 = Cancel alarm
0.5
5
minute
30
second
20
second
0.0
0.0
8
30
second
0
0=Celsius
1=Fahrenheit (not supported)

Werbung