Concentrate:
1. E2 alarm is effective only after meeting the start-up alarm delay (A1) or
entering the target temperature section (that is, between the set
temperature and the set temperature + refrigeration return difference F2)
after the thermostat is powered on
2. E3 alarm is effective only after meeting the start-up alarm delay (A1) and
after the thermostat is powered on, the water temperature enters the target
temperature section (that is, between the set temperature and the set
temperature + refrigeration return difference F2).
3. When the power on alarm delay A1 is set to 0,the E2 water temperature
ultra-high alarm will be triggered immediately when the water temperature
is super high when the power is turned on; When the power on water
temperature is ultra-low, the E3 water temperature ultra-low alarm is
triggered immediately
3. Relay output status when alarming:
1. When E1, E2, E3 alarm, the compressor and refrigerant solenoid valve
are controlled according to the normal control logic.
2. The water temperature setting (F0) of the controller when E4 alarm runs
according to the factory setting. When operating in constant temperature
mode, there is no E4 alarm.
3. When E5 alarms, the system automatically switches to the refrigeration
state.