Function monitoring with M12 connector
Using a two-channel analysis, function monitoring of the sensor can be implemented in
addition to level monitoring, e.g. per relay switch, PLC, AS-i Bus I/O module, ...).
When both outputs are connected, the MIN and MAX outputs assume opposite states when
the device is operating fault-free (XOR). In the event of an alarm condition or a line break,
both outputs are deenergized.
Connection for function monitoring with antivalence
2
1
3
4
K1
K2
L–
LED lit
LED not lit
Fault or warning
K1 / K2
external load
56