Max. permissible output of fans exceeded
Door fans will not function until the next DC reset
Cause:
Remedy:
Cause:
Remedy:
Cause:
Remedy:
558
Inverter feature has been deactivated
Cause:
Remedy:
559
Low Voltage Ride Through active
Cause:
Remedy:
Cause:
Remedy:
560
Power reduction due to over-frequency
Cause:
Remedy:
Cause:
Remedy:
561
Power reduction due to over-temperature
Cause:
Remedy:
Cause:
Remedy:
Cause:
Remedy:
98
Door fan defective
Replace fan
Faulty cable connection to door fan
Check cable connection
Measurement circuit on Snowball defective
Replace Snowball
The software version of the individual components does not support some
features
Update software
The inverter attempts to stay connected to the grid for grid support despite
voltage dip
Remedied automatically
Strong voltage dip on the public grid
Check grid parameters
An over-frequency was detected, for grid support the effective power of the
inverter is reduced
Remedied automatically
Over-frequency on the public grid
Check grid parameters
Blocked air supply
Clear ventilation grille
Increased ambient temperature
Change installation location / Install external cooling
Installation distance between the inverters too small
Increase distance