Herunterladen Inhalt Inhalt Diese Seite drucken

Performing The Inspection - Awg Fd Z2 Originalbetriebsanleitung

Vorschau ausblenden Andere Handbücher für FD Z2:
Inhaltsverzeichnis
Verfügbare Sprachen

Verfügbare Sprachen

AWG | Fittings | Inductors FD Z2 and Z4
6 .2

Performing the inspection

CAUTION
Performing the inspection safely
Some inspection steps are performed with pressurised systems.
– Observe the safety regulations.
– Wear personal protective equipment.
– Do not put other persons in danger.
6 .2 .1
BASIC Inspection after each use
1. Inspect the inductor for visible damage.
2. Check the pick tube (accessory) for contamination and damage.
6 .2 .2
STANDARD Inspection every 12 months
1. Leak test at 10 bar inlet pressure.
6 .2 .3
ADVANCED Inspection every 12 months
>
Check the coupling torque of the Storz adapter:
Threshold value
If the coupling torque is below the applicable threshold value, the
adapter must be replaced.
>
Threaded version: Check the thread for heavy wear and tear. Replace
device if worn.
37
Storz 52 (C): 1.5 Nm
Storz 75 (C): 2.5 Nm
functional tESt
M1008B10 | Rev. 03-08/24

Kapitel

Inhaltsverzeichnis