Rinsing and uncoupling the inductor
1. Shut off the water supply.
2. Interrupt the supply of foam agent.
3. Open the water supply and the hand lever at the foam nozzle.
4. During rinsing, switch the setting sleeve through all settings in order
to ensure that all internal suction bores are cleaned.
Important Do not aspirate dirty water or foam concentrate to ensure
5. As soon as only clear water and no more extinguishing foam emer-
ges from the foam nozzle, close the hand lever. If necessary, perform
multiple rinsing passes.
6. Shut off the water supply and, by hand or with the use of a coupling
spanner, detach the input and output side couplings from the fixed
coupling.
Important Water may emerge when the coupling is released.
5 .3

Visual inspection after each use

The inductor is separated from the water supply.
9
The inductor must not be contaminated with foam agent. If necessary,
9
rinse the inductor again as described in the previous section.
1. Check the inductor and the pick tube (accessory) for visible damage.
Important Do not continue to use damaged components!
35
that the suction holes do not get clogged.
If you discover any damage, this must be reported
to the person or department responsible.