Registers
AIRZONE MODBUS RTU AND AIRZONE MODBUS TCP/IP MAP
Suitable for installations containing systems and/or Aidoo Pro.
EN
Airzone
Note: Available for Airzone systems, Webserver.
•
System registers
In systems, 25 16-bit input/output registers are defined.
•
Zone registers
In the registers associated with zones, the address of the same is calculated as follows:
ZONE_REGISTER_ADDRESS = (BASE_ZONE x 256) + REGISTER_RELATIVE_ADDRESS
The zone address identifies the zones associated to a unit, between 1 and 32 (up to 32*
possible zones associated to the same unit). Address 127 is reserved for Broadcast to all the
zones of the same unit and is only valid for write functions.
Note: The total number of zones depends on the system (see System identification section).
Fourteen 16-bit zone registers are defined.
Aidoo
Note: Available for Aidoo Pro systems.
•
System registers
In systems, 3 16-bit input/output registers are defined.
•
Zone registers
In Aidoo for direct expansion units and fancoil units, the zone address is always 1. In Aidoo
for air to water units, there can be up to 2 zones. Therefore, the zone register address is
calculated as follows:
ZONE_REGISTER_ADDRESS = (BASE_ZONE x 256) + REGISTER_RELATIVE_ADDRESS
20
ACCESS THE OBJECT TABLE.