Read commands

Request
Byte
0
System address (1-247) (0: Broadcast)
1
2
EN
3
4
5
6
7

MODBUS RTU AIDOO

Write commands

Write to single register
Provided no error occurs, the response must be in exactly the same format as the write
command.
18
Field
Read registers (3/4)
Zone address
Start register address
Number of registers to read (N)
CRC
Byte
0
1
2
3
4
5
6
7
Response
Byte
0
1
2
3
4
3 + 2·N
4 + 2·N
5 + 2·N
6 + 2·N
Field
Secondary address (1-247) (0: Broadcast)
Write to single register (6)
Register address
Data to write
CRC
Field
System address (1-247) (0: Broadcast)
Read registers (3/4)
Number of response bytes (2·N)
Data to read from register 0
...
Data to read from register N
CRC