Levelflex M
Tab. 3
Electrical data:
Power supply circuit:
Voltage version
Supply voltage
Max. power
Um =
Signal circuit in protection type: intrinsic safety EEx ia IIB or EEx ib IIB
For installation as per EN 60079-14 for connection to a certified intrinsically-safe circuit with the following maximum values:
FMP40-... in version:
a)
effective inner inductance
a)
effective inner capacitance
a)
permitted outer capacitance at
for electric circuit in category ia
a)
permitted outer capacitance
for electric circuit in category ib
a)
Comment on
:
If the signal circuit (active or passive) is situated in Zone 21 or Zone 22 and the electrical connection is protected by means of
suitable measures against mechanical damage (short-circuit / interruption), the values for the inner and permitted outer
inductances and capacitances corresponding to material group IIB do not have to be taken into consideration.
The measure for energy limitation by means of intrinsic safety (ia or ib, depending on the application) is not affected by this.
Tab. 4a FMP40
Thermal data:
An irreversible thermal fuse with cut-off temperature of 115 °C is implemented in the FMP40 4-wire transmitter
Maximum permitted ambient temperature
Maximum surface temperature
at 40 °C ambient temperature
Maximum surface temperature
at 80 °C ambient temperature
Maximum surface temperature for probe ambient
temperatures > 80 °C and under simultaneous
compliance of the ambient temperature at the
electronics housing in accordance with Tab. 1a
Endress+Hauser
AC
90...253 VAC 50 / 60 Hz
3.5 VA
253 VAC
active
Uo = 21.4 V
Io = 237.48 mA
Po= 1.271 W
Ri = 90.1 ohms
Characteristic curve: linear
Permanent values: Io = 85 mA
Po= 1.17 W
Li = negligible
Ci ≤ 10 nF
La = 0.15 mH Ca ≤ 1 µF
La = 0.5 mH Ca ≤ 870 nF
La = 1 mH Ca ≤ 840 nF
La = 3 mH Ca ≤ 810 nF
La = 3 mH
Ca = 1.22 µF
Probe
in
Category 1 (Zone 20)
-40 °C .....+150 °C
+40 °C
+80°C
.....+150 °C
(identical to process temperature)
XA 168F-C
DC
10.5....32 VDC.
1 W
60 VDC
passive
Ui = 30 V
Ii = 300 mA
Pi = 1.2 W
Ri ≥ 8.7 Ω
Li ≤ 2 mH
Ci ≤ 10 nF
n.a
n.a
Electronics housing
in
Category 2
Category 3
(Zone 21)
(Zone 22)
-40 °C .....+80 °C
+ 80 °C
+ 115 °C
+ 115 °C
+ 43 °C
+ 83 °C
+ 83 °C
5