Herunterladen Inhalt Inhalt Diese Seite drucken

Electrical Wiring - Riello Rg0.R 367 T1 Installations-, Bedienungs- Und Wartungsanleitung

Inhaltsverzeichnis
Verfügbare Sprachen
  • DE

Verfügbare Sprachen

3.4 ELECTRICAL WIRING

WARNING
DO NOT EXCHANGE NEUTRAL WITH PHASE
~
50Hz 230V
PE L
N
Safety
thermostat
7 pin plug
7 pole socket
D1888
Ignition
electrodes
CONTROL BOX
To remove the control-box from the burner, loosen screw (A, Fig. 9)
after removing all components, the 7 pin plug and earth wire.
In case of disassembly of the control box, retighten the screw
(A) with a torque wrench setting of 1 – 1.2 Nm.
2596
Main switch
T6A
Limit
thermostat
Brown
Blue
Black
White
Blue
Heater with start
thermostat
Burner-earth
NOTES:
– Wires of min. 1 mm
otherwise by local standards and legislation).
– The electrical wiring carried out by the installer
must be in compliance with the rules in force in
the Country.
Hour counter
(230V - 0.1A max.)
Remote lock-out signal
(230V - 0.5A max.)
Flame sensor
Oil valve
Air damper
coil
Motor
5
GB
2
section. (Unless requested
TESTING
Check the shut-down of the
burner by opening the thermo-
stats and the lock-out by dark-
ening the flame sensor.
Capacitor
Fig. 9
S7186
A
Inhaltsverzeichnis
loading

Diese Anleitung auch für:

Rg0.1r 368 t137365503736750

Inhaltsverzeichnis